121/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
12 Actuators X53 / X54
25.09.2013
12.3 Referencing
An incremental transducer is used for position feedback. This means that referencing of
the actuators must be performed after power-ON. In addition, at the end of each
shutdown in phase 10, the actuators are referenced to ensure that individual stepping
errors, which could lead to shutdown, do not accumulate. If a position error occurs, the
system switches to the safety phase (phase 01), enabling the actuators with detected
position errors to be referenced. During the following phase 10, the only actuators
referenced are those that were not referenced before in the safety phase (phase 01).
The position of the reference point can be selected depending on the type of burner,
either the
Closed
position (<0°) or the
Open
position (>90°).
When using actuators SQM33.6 or SQM33.7, the actuator type (parameter 613) must
be set (refer to chapter
Actuator type / running time
).
Note!
If a SQM33.7 is used, the modulating operating ramp (parameter 544) may need to be
increased (refer to chapter
Running speed / maximum curve slope
).
Listed below settings for air apply to both fuels:
In single-fuel operation or in dual-fuel operation, the parameters 601...606 and 611
are assigned to fuel 0
In dual-fuel operation, the parameters 608...610 and 612 are assigned to fuel 1