198/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
28 Parameter level
25.09.2013
28.11.4 Warm settings for modulating operation («G mod», «Gp1 mod», «Gp2
mod» and «Lo mod»)
Note
With the
warm settings
, the burner is started up after pressing the
Info
button. Air-fuel ratio
control can now be accurately set while the flame is present. When traveling along the
precalculated curve to high-fire point
P9
,
all intermediate curvepoints (
P2…P8
) must be set.
Automatic operation is released when – after reaching
P9
– the curve settings are quit
by
pressing
ESC
. If the curve settings are aborted earlier (
ESC
or shutdown due to fault),
prevention of startup
OFF UPr
continues to be active until all points are set.
If required, the gas pressure can be set at the high-fire point. In case the gas pressure is
changed, all points must be checked by traveling along the curve downward and – if required
– readjusted.
P
V
h min s
%
B
ild 113
/0
707
Identification of start for setting the curve parameters.
The display shows
run Gas0
or
run Gas1
or
run Oil0
or
run Oil1,
depending on the type of fuel currently
burnt or the type of fuel train.
/reset
When there is a request for heat.
Note
If, during the time the curve is parameterized, an error occurs which leads to safety shutdown,
parameterization of the curve is quit.
P
V
h min s
%
B
ild 114
/0
707
Phase
Standby
(stationary)
P
V
h min s
%
B
ild
1
0
/0
70
7
Phase
Fan ramp up
(fan motor = ON, safety valve = ON)
P
V
h min s
%
B
ild
1
1
5/
07
0
7
Phase
Traveling to prepurge
position
P
V
h min s
%
B
ild 116
/0
707
Phase
Prepurging