6.2.2.7
Minimum air clearances
After proper installation, verify that the minimum air clearances between non-insulated parts
are maintained. Be aware of any protruding wire ends.
Table 6-2
Minimum air clearance dependent on rms value of the alternating voltage U
rms
Rms value of the alternating voltage U
rms
Minimum air clearance
mm
≤ 250 V
3.0
≤ 500 V
3.0
≤ 630 V
5.5
≤ 1000 V
8.0
Values apply at an installation altitude of up to 2000 m.
When determining the required minimum air clearance, the voltage value in the table may be increased by
a factor of 1.1, so that the rated input voltage range is taken into account during general use.
6.2.3
Screw-type connections with connecting thread
Cable glands with connecting thread in the terminal box (EN 50262)
②
O ring
6.3
Tightening torques
Note the information in Chapter Tightening torques (Page 133).
6.3.1
Cable entries, sealing plugs and thread adapters
Note the following when mounting:
• Avoid damaging the cable jacket.
• Adapt the tightening torques to the cable jacket materials.
Electrical connection
6.3 Tightening torques
1LE5, 1PC4 shaft heights 280 ... 355
70
Operating Instructions, 11/2022, A5E41454666A