8.7.2
Electrical faults
Note
If you are operating the motor with a converter, the operating instructions of the converter must
also be observed if electrical faults occur.
Table 8-1
Electrical faults
↓ Motor fails to start
↓ Motor accelerates sluggishly
↓ Rumbling noise during startup
↓ Rumbling noise during operation
↓ High temperature rise during no-load operation
↓ High temperature rise with load
↓ High temperature rise of individual winding sections
Possible causes of faults
Remedial measures
X
X
X
X
Overload
Reduce the load.
X
Interrupted phase in the supply cable
Check the switches and cables.
X
X
X
X
Interrupted phase in the feeder cable af‐
ter switching on
Check the switches and cables.
X
Mains voltage too low, frequency too
high
Check the power supply conditions.
X
Mains voltage too high, frequency too
low
Check the power supply conditions.
X
X
X
X
X Stator winding incorrectly connected
Check the winding connection in the terminal
box.
X
X
X
X Winding short circuit or phase short cir‐
cuit in stator winding
Determine the winding resistances and insulation
resistances. Carry out repair work after consulta‐
tion with the manufacturer.
X
Incorrect direction of rotation
Check the connection.
Operation
8.7 faults
1LE5, 1PC4 shaft heights 280 ... 355
94
Operating Instructions, 11/2022, A5E41454666A