Non-standard tightening torques
Different tightening torques for electrical connections and bolted connections for parts with
flat seals or insulating parts are specified in the relevant sections and drawings.
A.1.2
Terminal board and grounding
Table A-2
Tightening torques for electrical connections on the terminal board and grounding
Thread ∅
M3.5
M4
M5
M6
M8
M10
M12
M16
Nm
min.
0.8
0.8
1.8
2.7
5.5
9
14
27
max.
1.2
1.2
2.5
4
8
13
20
40
A.1.3
Terminal boxes, end shields, grounding conductors, sheet metal fan covers
If no other tightening torques are specified, then the values in the following table apply.
Table A-3
Tightening torques for screws on the terminal box, end shields, screw-type grounding conductor connections
Thread ∅
M3.5
M4
M5
M6
M8
M10
M12
M16
M20
Nm
min.
0.8
2
3.5
6
16
28
46
110
225
max.
1.2
3
5
9
24
42
70
165
340
A.1.4
Cable glands
Note
• Avoid damaging the cable jacket.
• Adapt the tightening torques to the cable jacket materials.
Technical specifications
A.1 Tightening torques
1LE5, 1PC4 shaft heights 280 ... 355
134
Operating Instructions, 11/2022, A5E41454666A