General Information Regarding the Wiring
72
Hardware Description 0360520xx
11.3
Motor Cable
Use shielded conductors for the motor in order to keep interference as low as possi-
ble (line cross-section according to the table). If possible, the shield should be con-
nected with both ends and largest surface. If this is not possible, the shield should be
connected with one end to the shield bar which can be supplied by SIEB & MEYER.
Warning
Earth conductors additionally lead in motor cables must directly be
put to the earth shield and be marked with
7
.
If the procedure turns out to be impracticable, omit the earth conduc-
tor connection in the motor cables and wire a separate earth conduc-
tor in parallel to the motor cables preventing disturbing ground loops.