Functional Description of the Connectors/Interfaces
48
Hardware Description 0360520xx
sinudyn-36
8.2.12
X40 - Restart Lock According to Safety Category 4 / SIL 3
Valid up to device version 0003:
X
6-pole MiniCombiCon
If no restart lock is used, the wiring can be carried out as follows:
Pin
Function
1*
Monitoring 1 / SAVE
2
Monitoring 2 / SAVE RETURN-
3
+ 24 V power supply for monitoring
4
OSSD 1 / SVI - + 24 V +/- 20 % -
5
0 Volt / SVI -
6
OSSD 2 / SVII - + 24 V +/- 20 % -
*
Pin 1 is coded.
Warning
OSSD 1 and OSSD 2 must always be connected to pin 4 and pin 6
and 0 V must always be connected to pin 5. If the restart lock is not
used all pins 4 and pins 6 must be connected to + 24 V and all pins 5
must be connected to 0 V.
Warning
If the restart lock is to be used, please take the information from
chapter "Restart Lock“ on
into account!