8014865/ZUJ3/2018-11-29 • © SICK AG • Subject to change without notice 23
Commissioning
7 Commissioning
7.1
Ultrasonic sensors with switching outputs
→
For a graphical overview of the various setup options,
see Page 49, Chapter 13.1 and Page 50, Chapter 13.3.
7.1.1
Teach-in the switching point – method A
Distance to object (DtO)
In method A, the switching output is set when the object is located within
the taught-in switching range. The orange LED lights up when the switching
output is active.
1
Fig. 8: Teach-in the switching point – method A
1
Switching point
1. Position object at
1
.
2.
Apply "L+" to "MF" for approximately 3 seconds until both LEDs flash
simultaneously.
3.
When both LEDs flash alternately, apply "L+" for approximately
1 second to "MF".
b
The ultrasonic sensor's switching point has been taught-in.
The ultrasonic sensor is in normal operational mode.
Configure the switching output as normally closed or normally open.
→
7.1.2
Teach-in the switching point – method B
Distance to object (DtO)
In method B, the switching output is set when the object is located within
the taught-in switching range plus 8 %. The orange LED lights up when
the switching output is active.
1
+ 8 %
Fig. 9: Teach-in the switching point – Method B
1
Switching point