IO-Link interface
34
© SICK AG • Subject to change without notice • 8014865/ZUJ3/2018-11-29
8.3.2
SICK-specific UM18-21712A21_
Index
decimal
(hex)
Description
Format
Access
Value range
Example
Remarks
64 (0x40)
Switching point 1
UINT16
R/W
306 ... 3609
(21 ... 248 mm)
320 corresponds
to
22 mm
Specify values
as a multiple
of the internal
measurement value
resolution (0.069 m).
65 (0x41)
Switchback point 1 UINT16
R/W
320 ... 3624
(22 ... 249 mm)
71 (0x47)
Switching point 2
UINT16
R/W
335 ... 65512
1)
(23 ... 250 mm)
72 (0x48)
Switchback point 2 UINT16
R/W
335 ... 65512
1)
(23 ... 250 mm)
73 (0x49)
Foreground
suppression
UINT8
R/W
0 ... 1878
(0 ... 129 mm)
66 (0x42)
Switching output
function
UINT8
R/W
• 00: normally closed
• 02: normally open
–
67 (0x43)
Filter
UINT8
R/W
• 00: F00
2)
• 01: F01
• 02: F02
→
See also
68 (0x44)
Filter strength
UINT8
R/W
• 00: P00
• 01: P01
• 02: P02
• 03: P03
• 04: P04
• 05: P05
• 06: P06
• 07: P07
• 08: P08
• 09: P09
For the selected
measured value filter,
you can select a filter
strength between 0
(weak filtering effect)
and 9 (strong filtering
effect).
74 (0x4A)
Teach via pin 5 in
SIO mode
UINT8
R/W
• 00: deactivated
• 16: activated
–
Teach
Index
decimal
(hex)
Description
Format
Access
Value range
Example
Remarks
02 (0x02)
TEACH
UINT
W
• 161: Method A
• 162: Method B
• 164: Two-way
reflection barrier
• 168: Reset to
factory setting
A teach overwrites
a function that has
already been set with a
newly selected function.
If a teach is successful,
the old value is
retained.
→
1) Window operation deactivated for values > 3638.
2) Operation with filter setting "F00" is not permitted, as EMC faults may occur in this case.
Table 12: SICK-specific service data UM18-21712A21_