Commissioning
26
© SICK AG • Subject to change without notice • 8014865/ZUJ3/2018-11-29
1. Position object at
1
.
2.
Apply "L+" to "MF" for approximately 3 seconds until both LEDs flash
simultaneously.
3.
When both LEDs flash alternately, position object at
2
.
4. Apply "L+" to "MF" for approximately 1 second.
b
The analog output has been taught-in. The ultrasonic sensor is in
normal operational mode.
NOTE!
You can teach-in the limit near the sensor or the limit
away from the sensor first. You can teach-in the output
characteristics afterwards.
→
See the following section.
7.2.2
Configuring the rising or falling output characteristic curve
Factory setting: "Rising output characteristic curve"
1.
Apply "L+" to "MF" for approximately 13 seconds until both LEDs flash
alternately.
2.
The green LED flashes. The orange LED indicates the current setting:
• On: Rising output characteristic curve
•
Off: Falling output characteristic curve
3.
To change the setting, apply "L+" to "MF" for approximately 1 second.
The orange LED changes its status.
4.
After configuring, wait approximately 10 seconds until the green LED
stops flashing.
b
The setting has been applied. The ultrasonic sensor is in normal
operational mode.
7.3
Additional settings for all sensor models
7.3.1
Switching between teach-in and synchronization/multiplex mode
NOTE!
The teach-in functionality is deactivated when
synchronization/multiplex mode is activated.
For synchronization/multiplex mode, the ultrasonic
sensors must be interconnected via the "MF" input (pin
5). You can operate a maximum of 20 UM18-2 Pro
sensors in synchronization/multiplex mode.