SICK LSI Technical Description - 06/98
Fault code:
Cause / What to do:
202
Same levels at input C:
Check input levels at input C1 and C2. Levels must be inverse to each other.
203
Same levels at input D:
Check input levels at input D1 and D2. Levels must be inverse to each other.
204
Faulty operation of inputs:
Check operation.
206
Incorrect operation of RES A:
Check level and time response of RES A.
208
Incorrect operation of RES B:
Check level and time response of RES B.
209
Input frequency of incremental encoders above 100 kHz:
Check configuration of incremental encoders.
240
Contactor monitor EDM A still open:
Check contactor monitor EDM A.
242
Contactor monitor EDM A closed when output active:
Check contactor monitor EDM A.
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
243
Contactor monitor EDM A open when output inactive:
Check contactor monitor EDM A.
Switch power off and back on again.
Replace the LSI, or contact SICK Service..
244
Contactor monitor EDM B still open:
Check contactor monitor EDM B.
246
Contactor monitor EDM B closed when output active:
Check contactor monitor EDM B.
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
247
Contactor monitor EDM B open when output inactive:
Check contactor monitor EDM B.
Switch power off and back on again.
Replace the LSI, or contact SICK Service.
248
Object in protective field:
Check ambient conditions.
Adapt LSI configuration to ambient conditions.
249
Object in warning field:
Check ambient conditions.
Adapt LSI configuration to ambient conditions.
250
Internal error:
Switch power off and back on again.
Replace the LSI, or contact SICK Service