45
SICK LSI Technical Description - 06/98
9.8 Simulate monitoring cases
You can check the settings of the monitoring cases by simulating
the input conditions of each individual monitoring case on your
PC. In this way you can check whether sensors and fields are
correctly assigned in every monitoring case.
•
From the menu choose
LSI - Monitoring Cases - Simulate
.
•
Or choose the Simulate Monitoring Cases button from the
toolbar.
A dialog box appears displaying the logged-on sensors.
•
For the available inputs (A, B, C, D) define the desired state:
0
low
1
high
•
If you have connected incremental sensors, check the
Speed checkbox and enter the speed you want in the list.
The dialog box shows the monitoring cases active under these
input conditions: the active monitoring area appears in the
window of the sensor to which it is assigned for the monitoring
case in question.
In the example two sensors are present. Under the pre-set input
conditions two monitoring cases are active at once
(simultaneous monitoring case).
The names of the active monitoring cases are shown in the
status bar at the bottom of the dialog box.