An OR operator is applied to the process data for the outputs AUX_OUT of the individual
Flexi Loop nodes and the logic states of the parameter
AUX_OUT from MSTR AUX_IN
.
b
Set the parameter
AUX_OUT from MSTR AUX_IN
to
Off
.
b
Save the configuration using Store
9)
.
✓
The output AUX_OUT of the Flexi Loop node is no longer linked to the AUX_IN of
the MSTR2 Flexi Loop accessory.
Flashing mode 1 or 2
Flash modes 1 and 2 can be used to have lamps at the non-safe outputs of the Flexi
Loop nodes flash at a frequency of 1 Hz or 2 Hz.
b
Set the parameter
Flashing mode 1
or
Flashing mode 2
to
On
.
b
Save the configuration using Store
9)
.
✓
If the output AUX_OUT of the Flexi Loop node is activated, then it is operated at
1 Hz or 2 Hz.
7.4.2.2
Configuration of the Flexi Loop string
DANGER
Hazard due to disabling the protection against tampering!
If you disable the protection against tampering, then a Flexi Loop node can be removed
or jumpered. In this situation the safe sensor cascade switches on despite the change.
Only disable the tamper protection if imperative for the implementation of the applica‐
tion. In this case prevent possible tampering by other measures (e.g. protected cable
laying).
Setting commissioning mode
If necessary, deactivate a taught-in configuration by setting the MSTR2 Flexi Loop
accessory to commissioning mode.
b
Log into the configuration software for the standard controller as
Specialist
.
b
Change to
Parameter
on the IO-Link port used.
b
Open the
Parameter Menu
branch there.
✓
The commands and parameters contained in the IODD are displayed.
b
Open the
Edit Config. Data
branch.
b
Expand the
Edit MSTR settings
branch.
✓
The system displays the configuration options for the MSTR2 Flexi Loop accessory.
b
On the
Commissioning mode
menu select the
True
option.
b
Save the configuration using Store
9)
.
✓
The MSTR2 Flexi Loop accessory changes to the
Waiting for configuration
mode.
Disabling tamper protection
Define whether the number and types for the Flexi Loop nodes are to be checked on
power up.
b
Open the
Edit Config. Data
branch.
b
Expand the
Edit MSTR settings
branch.
✓
The system displays the configuration options for the MSTR2 Flexi Loop accessory.
b
On the
Ignore node count
menu select the
True
option.
b
Save the configuration using Store
9)
.
✓
With immediate effect the number of Flexi Loop nodes will
not be checked
.
b
On the
Ignore node types
menu select the
True
option.
9)
Applies for TwinCAT™, alternatively Store all User Data (SystemCommand 03h ParamDownloadStart - IO-Link Interface and System Speci‐
fication V.1.1 Table B.9).
7
CONFIGURATION
60
O P E R A T I N G I N S T R U C T I O N S | Flexi Loop
8015836/YT10/2016-05-24 | SICK
Subject to change without notice