Figure 57: Commands and parameters in the IODD
1
Parameter
2
Parameter Menu
7.4.2.1
Configuration of the Flexi Loop nodes
A safe sensor cascade can contain up to 32 Flexi Loop nodes. The logical numbering
2
starts after the MSTR2 Flexi Loop accessory
1
at the first Flexi Loop node connected
and ends with the terminator
3
.
Figure 58: Logical numbering of the Flexi Loop nodes
1
MSTR Flexi Loop accessory
2
Logical numbering of the Flexi Loop nodes and the terminator
3
Terminator
4
Flexi Loop accessories (in the example PWRI)
Flexi Loop accessories (in the example PWRI)
4
can be connected between the Flexi
Loop nodes. Flexi Loop accessories are not given a logical number.
Defining number and types
In the configuration from the factory the first position contains a Flexi Loop node
FLN-EMSS1100108 and the second position a terminator. You define the actual num‐
ber and the types of the Flexi Loop nodes.
b
Log into the configuration software for the standard controller as
Specialist
.
b
Change to
Parameter
on the IO-Link port used.
7
CONFIGURATION
58
O P E R A T I N G I N S T R U C T I O N S | Flexi Loop
8015836/YT10/2016-05-24 | SICK
Subject to change without notice