- 95 -
Insulation
resistance
10 M minimum, at 500 V DC
Dielectric
strength
Between power terminal and ground (GND): 1.5 kV AC for 1 minute
Between input terminal and ground (GND): 1.5 kV AC for 1 minute
Between input terminal and power terminal: 1.5 kV AC for 1 minute
Other
Power
consumption
ACD-13A: Approx. 18 VA
ACR-13A: Approx. 15 VA
Ambient
temperature
0 to 50 (32 to 122 )
Ambient
humidity
35 to 85 %RH (Non-condensing)
Weight
ACD-13A: Approx. 460
g
ACR-13A: Approx. 330
g
Accessories
included
For the ACD-13A and ACR-13A:
Mounting brackets: 1 set, Instruction manual: 1 copy
Gasket (Front mounted to the unit): 1 piece
For the ACR-13A only:
Harness EVT5:1 piece [When Event output (A5 option) is ordered]
Harness W: 1 piece [When Heater burnout alarm (W option) is ordered]
Harness W: 2 pieces [When Heater burnout alarm(W3 option) is ordered]
Harness E: 1 piece [When External setting input (EA , EV option)
is ordered]
Harness VT: 1 piece [When Transmission output (TA1, TV1 option)
is ordered]
Accessories
sold separately
Terminal cover
Heater burnout alarm 20 A: CT (CTL-6-S-H)
Heater burnout alarm 100 A: CT (CTL-12-S36-10L1U)
USB communication cable (CMB-001)
12.2 Optional Specifications
Event input (Option code: EI)
EVI1 to EVI4 are used as an Event input.
Any Events selected in [Event input allocation] will be performed depending on the
Input ON (Closed) or OFF (Open) status. See (Fig 6.3.3-1) on p.33.
If the Set value memory number function is selected:
2
0
, 2
1
, 2
2
and 2
3
will be allocated to Event input EVI1 to EVI4 respectively, and the Set
value memory number (SV1 to SV15) will be determined by each value of EVI1 to EVI4.
The selected Set value memory number, the added value of 2
n
+1, is indicated on the
MEMO/STEP Display. See Section “8.7 Set Value Memory Function” on pp.76, 77.
Circuit current when Closed
Approx. 16 mA
Event output (Option code: A3)
EVT1 to EVT3 are available using a common terminal.
The output will be turned ON or OFF depending on the conditions selected in [Event
output allocation].
Output
Relay contact, 1a
Control capacity: 3 A 250 V AC (Resistive load)
1 A 250 V AC (Inductive load, cos =0.4)
Electrical life: 100,000 cycles