![Shinko ACD-13A Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/shinko/acd-13a/acd-13a_instruction-manual_1258167091.webp)
- 91 -
Control action
OUT1
proportional
band
0 to Input span ( )
DC voltage, current inputs: 0.0 to 1000.0%
(ON/OFF control when set to 0 or 0.0)
(Factory default: 10 )
Integral time 0 to 3600 seconds (OFF when set to 0)
(Factory default: 200 seconds)
Derivative
time
0 to 1800 seconds (OFF when set to 0)
(Factory default: 50 seconds)
OUT1
proportional
cycle
1 to 120 seconds (Factory default:
Relay contact: 30 sec, Non-contact voltage: 3 sec,
Direct current: Not available)
ARW
0 to 100% (Factory default: 50%)
OUT1
ON/OFF
hysteresis
0.1 to 1000.0 ( ) (Factory default: 1.0 )
DC voltage, current inputs: 1 to 10000
(The placement of the decimal point follows the
selection.)
OUT1 high
limit
0 to 100% (Direct current: -5 to 105%)
(Factory default: 100%)
OUT1 low
limit
0 to 100% (Direct current: -5 to 105%)
(Factory default: 0%)
Control output
(OUT1)
Relay
contact
1a1b
Control capacity: 3 A 250 V AC (resistive load),
1 A 250 V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
Non-contact
voltage
(SSR drive)
12 V DC 15%
Maximum 40 mA (short circuit protected)
Direct
current
4 to 20 mA DC (Resolution: 12000)
Load resistance: Maximum 600
Standard functions
EVT1 output
The output is turned ON or OFF depending on the conditions
selected in [Event output allocation].
Output: Relay contact 1a
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
EVT2 output
The output is turned ON or OFF depending on the conditions
selected in [Event output allocation].
If D or P option is ordered, EVT2 output will be disabled.
Output: Relay contact 1a
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
Содержание ACD-13A
Страница 1: ...DIGITAL INDICATING CONTROLLERS ACD 13A ACR 13A INSTRUCTION MANUAL ...
Страница 126: ...126 7 8 9 10 11 12 13 14 15 ...