Group selection (Fixed value control)
(1) Proceed to the setting item of the desired Set value memory number in the
‘SV, Event group’.
(2) Set the following values:
SV, EVT1 alarm value, EVT1 high limit alarm value, EVT2 alarm value, EVT2 high
limit alarm value, EVT3 alarm value, EVT3 high limit alarm value, EVT4 alarm value,
EVT4 high limit alarm value, EVT5 alarm value, EVT5 high limit alarm value
[Registration complete]
• Data is registered in the file number indicated by the MEMO/STEP Display.
• When any number is retrieved by connecting terminals, the selected number will be
indicated, and the control is performed using the data (set values) of the indicated
file number.
• To change the set values, repeat [Operation procedure] on the previous page.