- 45 -
6.3.7 External Setting Group
Available only when the EA or EV option is ordered.
To enter the External setting group, follow the procedure below.
(1)
Set the
key 4 times in PV/SV Display Mode.
The unit enters the Engineering group.
(2)
Press the
key. The unit proceeds to the Input group.
(3)
Press the
key multiple times until characters of the External
setting group appear.
(4)
Press the
key.
The unit proceeds to the ‘Remote/Local’.
Character
Setting Item, Function, Setting Range
Factory Default
Remote/Local
Local
• Selects Remote or Local setting of the SV.
•
: Local (The SV can be set by front keypad.)
: Remote (The SV can be set in analog by the remote
operation externally.)
External setting input high limit
1370
• Sets External setting input high limit value.
[For EA1 (4-20 mA) option, the value corresponds to 20 mA input.]
• Setting range: External setting input low limit to Input range high limit
(The placement of the decimal point follows the selection.)
External setting input low limit
-200
• Sets External setting input low limit value.
[For EA1 (4-20 mA) option, the value corresponds to 4 mA input.]
• Setting range: Input range low limit to External setting input high limit
(The placement of the decimal point follows the selection.)
Remote bias
0
• During remote action, SV adds the remote bias value.
• Setting range: Converted value of 20% of input span
DC voltage, current inputs: 20% of scaling span (The placement
of the decimal point follows the selection.)