- 103 -
(Table 14-1)
Alarm Type
Setting Range
High limit alarm (Deviation setting) -(Input span) to Input span ( ) *1
Low limit alarm (Deviation setting)
-(Input span) to Input span ( ) *1
High/Low limits alarm
(Deviation setting)
0 to Input span ( ) *1
High/Low limits independent
(Deviation setting)
0 to Input span ( ) *1
High/Low limit range alarm
(Deviation setting)
0 to Input span ( ) *1
High/Low limit range independent
(Deviation setting)
0 to Input span ( ) *1
Process high alarm
Input range low limit to Input range high limit*2
Process low alarm
Input range low limit to Input range high limit*2
High limit with standby alarm
(Deviation setting)
-(Input span) to Input span ( ) *1
Low limit with standby alarm
(Deviation setting)
-(Input span) to Input span ( ) *1
High/Low limits with standby
(Deviation setting)
0 to Input span ( ) *1
High/Low limits with standby
independent (Deviation setting)
0 to Input span ( ) *1
*1: For DC voltage, current inputs, the input span is the same as the scaling span.
*2: For DC voltage, current inputs, input range low (or high) limit value is the same as
scaling low (or high) limit value.
PID setting mode
Character
Setting Item, Setting Range
Data
OUT1 proportional band
Setting range: 0 to Input span ( )
DC voltage, current inputs: 0.0 to 1000.0%
OUT2 proportional band
Setting range: 0.0 to 10.0 times (Multiplied value of
OUT1 proportional band)
Integral time
Setting range: 0 to 3600 seconds
Derivative time
Setting range: 0 to 1800 seconds
ARW
Setting range: 0 to 100%
Manual reset
Setting range: 1000.0
DC voltage, current inputs: The placement of the decimal
point follows the selection.
OUT1 rate-of-change
Setting range: 0 to 100 %/sec