![Shinko ACD-13A Скачать руководство пользователя страница 115](http://html.mh-extra.com/html/shinko/acd-13a/acd-13a_instruction-manual_1258167115.webp)
- 115 -
Output group
Character
Setting Item, Setting Range
Data
Output group
OUT1 proportional cycle
Setting range: 1 to 120 seconds
OUT2 proportional cycle
Setting range: 1 to 120 seconds
OUT1 high limit
Setting range: OUT1 low limit to 100%
(Direct current output: OUT1 low limit to 105%)
OUT1 low limit
Setting range: 0% to OUT1 high limit
(Direct current output: -5% to OUT1 high limit)
OUT1 ON/OFF hysteresis
Setting range: 0.1 to 1000.0 ( )
DC voltage, current inputs: 1 to 10000 (The placement
of the decimal point follows the selection.)
OUT2 cooling method
: Air cooling (linear characteristics)
: Oil cooling
(1.5th power of the linear characteristics)
: Water cooling (2nd power of the linear
characteristics)
OUT2 high limit
Setting range: OUT2 low limit to 100%
(Direct current output: OUT2 low limit to 105%)
OUT2 low limit
Setting range: 0% to OUT2 high limit
(Direct current output: -5% to OUT2 high limit)
Overlap/Dead band
Setting range: -200.0 to 200.0 ( )
DC voltage, current inputs: -2000 to 2000 (The
placement of the decimal point follows the selection.)
OUT2 ON/OFF hysteresis
Setting range: 0.1 to 1000.0 ( )
DC voltage, current inputs: 1 to 10000 (The placement
of the decimal point follows the selection.)
Direct/Reverse action
: Reverse (Heating) action
: Direct (Cooling) action