![Shinko ACD-13A Скачать руководство пользователя страница 114](http://html.mh-extra.com/html/shinko/acd-13a/acd-13a_instruction-manual_1258167114.webp)
- 114 -
C(W/Re5-26)
32 to
4199
Pt100
-328.0 to 1562.0
JPt100
-328.0 to 932.0
Pt100
-328 to
1562
JPt100
-328 to
932
Pt100
-148.0 to 212.0
Pt100
-148.0 to 932.0
0 to 20 mA DC
-2000 to 10000
0 to 10 mV DC
-2000 to 10000
-10 to 10 mV DC
-2000 to 10000
0 to 50 mV DC
-2000 to 10000
0 to 100 mV DC -2000 to 10000
0 to 1 V DC
-2000 to 10000
0 to 5 V DC
-2000 to 10000
1 to 5 V DC
-2000 to 10000
0 to 10 V DC
-2000 to 10000
Scaling high limit
Setting range: Scaling low limit to Input range high limit
DC voltage, current inputs: -2000 to 10000 (The
placement of the decimal point follows the selection.)
Scaling low limit
Setting range: Input range low limit to Scaling high limit
DC voltage, current inputs: -2000 to 10000 (The
placement of the decimal point follows the selection.)
Decimal point place
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
: 4 digits after decimal point
PV filter time constant
Setting range: 0.0 to 100.0 seconds
Sensor correction
Setting range: -200.0 to 200.0 ( )
DC voltage, current inputs: -2000 to 2000 (The
placement of the decimal point follows the selection.)
Содержание ACD-13A
Страница 1: ...DIGITAL INDICATING CONTROLLERS ACD 13A ACR 13A INSTRUCTION MANUAL ...
Страница 126: ...126 7 8 9 10 11 12 13 14 15 ...