10. Specifications

Ŷ

 Display

z

 Position indicator

Œ

Output display color (LED bar graph)

: Green

Œ

Display resolution/dot

: 5%/20 dots

z

 Data display

Œ

Display digit/color

: 5 digits/7 segments LED green display, Height of character: 14 mm

Œ

Display resolution

: 1% (position, target value of position), 0.1% (input)

Œ

Sampling cycle

: 0.2 seconds

Œ

Display range

: Position and deviation: 

-

10~110%, Input value: 

-

10.0~110.0%

z

 Status display

:  4~20, 0~20 mA

'&ȍ

Position display

(POSITION)/Green

Input display

(INPUT)/Green

Target value of position/deviation display

(DES/DEV)/Green

Manual action

(MAN)/Green

Reverse action

(RA)/Green

Opening action

(OPEN)/Green

Closing action

(CLOSE)/Green

External (DI) input

(DI1, 2, 3)/Green

Event action

(EV1, 2, 3)/Orange 

Stand-by action

(STBY)/Green

Communication status

(COM)/Green

Ŷ

 Control input

z

 Current/receiving impedance

:   4~20, 0~20 mA

'&ȍ

z

 Voltage/input impedance

:  1~5V, 0~5V, 0~10V

'&0ȍ

z

 Input filter

: 0~99 seconds

z

 Isolation

: Control input not insulated from feedback electric potential and DI input

Control input insulated from analog output

Ŷ

 Setting

z

 Setting system

: By key switches (6 keys) on front panel

z

 Setting/selection item

Œ

Display switching

: By 

DISP

key switch on front panel

Œ

Auto/manual switching

: By 

MAN/AUTO

 key switch on front panel

Œ

Zero/span adjustment

: Provided with Automatic adjustment function; manual adjustment is also possible 

(correction of potentiometer error)

Œ

Selection of control characteristics

: Direct (DA)/reverse (RA)

Œ

Control characteristics gain setting

: Input values corresponding to 0% position and 100% position (scaling function) or position values corresponding to 0% 

input and 100% input (scaling function)

Œ

Position limiter setting

: Higher limit value 1~100%, Lower limit value 0~99% (higher limit>lower limit)

Œ

Setting of speed

: 10~100% In the case of contact output, setting of speed is not possible.

Œ

Hysteresis

: 1/4 of dead band.  Fixed to 0.3% when dead band is less than 1.2% of input.

Œ

Dead band setting

: 0.5~10.0% of input signal (Initial value: 2.0%)

Œ

Keylock

: 3-stage lock

Ŷ

 Feedback

z

 Feedback potentiometer rating

$Q\EHWZHHQȍDQGNȍWKUHHZLUHW\SH

Ŷ

 Control output

z

 Output type

: Contact

240V AC 2A

 

     

 

Combination of SSR and contact 240V AC 2A

Ŷ

 External operation input (DI)

z

 Number of points

: 3 points (DI1, DI2 and DI3)

z

 Operable items

: (1) Individual assignment to RA, STBY and present position value is possible.

(2) Assignment to 7 preset position values by binary numerals is possible.

(3) Assignment to 3 present position values and individual assignment to one of RA,

STBY and preset position value is possible.

z

 Operation

: Put in action when no-voltage contact or open collector turns ON.

Ŷ

 Event output (option)

z

 Number of event points

: 3 points (EV1, EV2 and EV3)

z

 Types

: Value of Position (higher limit, lower limit, hysteresis variable and stand-by action selectable), 

Input (higher limit, lower limit, hysteresis variable and stand-by action selectable), 

Operation, manual, potentiometer error, input error, and control loop trouble.

z

 Output rating/structure

: 240V AC 1A Resistive load / "a" contact

z

 Action display

: When EV1~EV3 are in action, orange lamp lights.

Ŷ

Analog output (option)

z

 Number/type

: 1 point, either position or control input to be selected 

z

 Analog output/rating

:  4~20 mA

)6/RDGUHVLVWDQFHȍRUOHVV

z

 Output scaling

:

Inverse scaling possible (lower limit

higher limit)

z

 Output accuracy

: ±0.5% FS or less 

z

 Isolation

: Analog output insulated from control input and feedback potentiometer

Ŷ

 Square root extraction (option)

z

 Position output control by square root extraction of input signals

Ŷ

 Communication function

z

 Communication type

: RS-232C, RS-485

z

 Communication system

: RS-232C/3-line type half duplex system, RS-485/2-line type half duplex multi-drop (bus) system

z

 Communication rate

: Half duplex asynchronous system

z

 Communication rate

: 1200, 2400, 4800, 9600, 19200 bps

Ŷ

 General specifications

z

 Data storage

: Non-volatile memory

z

 Operating ambient temperature/

     humidity range

:

-

aႏ5+RUOHVVQRGHZFRQGHQVDWLRQ

z

 Storage temperature

:

-

aႏ

z

 Supply voltage

: 100~240V AC±10% 50/60Hz

z

 Power consumption

: 13VA (240V AC)

z

 Conformity with standards

Safety

EMC

: IEC61010-1 and EN61010-1

: EN61326-1

z

 Insulation resistance

:  Between input/output terminals and power terminal  

500V  DC  

0ȍRUDERYH

Between power terminal and ground terminal  

500V  DC  

0ȍRUDERYH

z

 Dielectric strength

: Between input/output terminals and power terminal 

3000V  AC

1 minute 

z

 Protective structure

z

 Material of case

z

 External dimensions

z

 Mounting

z

 Panel thickness

z

 Panel cutout

z

 Weight

Between power terminal and ground terminal  1500V

 

AC

 

1 minute

 

:

 

Only front panel has dust-proof and drip-proof structure. (IP66 equivalent)

 

:

 

PP

E

 resin molding (equivalent to UL 94 V-1)

:

 

H96 

™

 W96

™

 

  D111 (Panel depth: 100) mm

:

 

Push-in panel (one-touch mount)

:

 

1~4 mm

:

 

92

 

™

  92 mm

:

 

Approximately 460 g

- 24 -

IEC61010-2-030 and EN61010-2-030

Temperature and Humidity Control Specialists

Head Office: 2-30-10 Kitamachi, Nerima-ku, Tokyo 179-0081 Japan 

Phone: +81-3-3931-7891    Fax: +81-3-3931-3089 

E-MAIL: [email protected] URL: https://www.shimaden.co.jp 

The contents of this manual are subject to change without notice. 

Содержание EM70

Страница 1: ...alog Output Type 17 9 Communication Setting 17 10 Input Range Setting 18 11 Input Filter Setting 18 12 Setting of Input Scaling Position Scaling 18 13 Position Limiter Setting 18 14 Motor Action Time...

Страница 2: ...The alert mark on the plate affixed to the instrument On the terminal nameplate affixed to the case of this instrument the alert mark is printed This is to warn you of the risk of electric shock whic...

Страница 3: ...5 16 17 OPEN 2A240VAC CLOSE COM 2A240VAC M3 M2 M1 SSR 26 TERMINAL 1 SPECIFICATION 27 28 SG SD RD SG RS 232C RS 485 Follow 3 5 Terminal Layout and 3 6 Terminal Arrangement Table and make sure to conduc...

Страница 4: ...iring is shown Particular attention should be paid to common lines and polarity INPUT DC Power supply for motor Power supply for EM70 100 240V AC 50 60Hz L N CW CW Clockwise CCW Counterclockwise Poten...

Страница 5: ...changes the display in the following order Position value input value target position value deviation value position value Display returns to the initial screen of a screen group such as 1 0 or 1 00 z...

Страница 6: ...e direction of revolution involves danger Correct the wiring if that is the case with reference to Cause of Trouble and Troubleshooting You should also confirm the positions of the control motor in th...

Страница 7: ...al input from control motor or an input error error of input signal from controller can be set Selectable from 3 types Suspension stand by action closing and opening of motor by setting its action tim...

Страница 8: ...md EXE Value of position 7 Value of position 6 0 50 0 51 0 60 0 70 Individual 3 points setting 7 values of position setting 3 values of position and individual 1 point setting Individual setting Valu...

Страница 9: ...tment Event 1 type setting Manual adjustment 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 13 1 14 1 15 1 16 1 17 1 25 1 26 1 27 1 28 1 00 1 Span side manual adjustment 1 00 2 The 1 0 zero span automatic adjustme...

Страница 10: ...ghts DISP DISP DISP DISP 0 0 Basic screen Present position value is displayed in 0 0 1 Control input value display screen Control input is displayed in 0 0 2 Target position value display screen Targe...

Страница 11: ...events allowing event set values to be set i e higher and lower limits of position and higher and lower limits of inputs as shown below 4 types of alarms Lower limit of position Higher limit of posit...

Страница 12: ...individually 7 preset position values are set for DI1 DI2 and DI3 3 preset position values are set for DI1 and DI2 and for DI3 one is selected from no rA St and Pr About DI type action and setting ra...

Страница 13: ...n to allow you to set only when Pr is selected as the value of position on the 0 51 052 and 0 53 external operating input screen 7 Setting of 7 point External Operating Input Position Value Initial va...

Страница 14: ...g range 0 100 7 4 Screen group 1 and parameter setting There are various apparatus that have relation to the settings in screen group 1 Please have a person who is familiar with the apparatus conduct...

Страница 15: ...justment screen which blinks while adjustment is going on 2 Set the motor to the zero position usually full close by the use of and keys When the key is pressed for registration the display changes to...

Страница 16: ...7 screen Event 3 type setting screen Initial value The same as event 1 Event 3 hysteresis setting screen Initial value 0 1 Setting range 0 1 5 0 The same as event 1 Event 3 stand by action setting scr...

Страница 17: ...except manual operation Communication address setting screen Initial value 1 Setting range 1 99 In case a plurality of controllers are linked for communication addresses need to be set individually to...

Страница 18: ...ling lower limit setting screen Initial value 0 Setting range 10 109 lower limit higher limit 100 0 20 80 100 Input scaling n o i t i s o P n o i t i s o P Input 100 75 15 0 0 1 0 Position scaling Inp...

Страница 19: ...ue Keylock of screen groups 1 and 2 All keylock except manual operation All keylock In case manual operation is set before setting keylock however operation by and keys is possible 1 38 Key Operation...

Страница 20: ...occur simultaneously the position error is given preference and the control loop error check is released Refer to the following formula in setting the control loop error detection time Set value of c...

Страница 21: ...iometer of control motor or for control signals Erroneous setting of output characteristic DA RA Correct wiring to potentiometer of control motor terminals 4 5 and 6 or for control signals terminals 1...

Страница 22: ...on of control loop error to a somewhat larger value Input higher limit error Control input signal exceeds higher limit 110 in HH Mismatch between input range and control input signal Problem with inpu...

Страница 23: ...3 type setting Event 3 hysteresis Event 3 stand by action Control at the time of position error Opening closing time at the time of position error Control at the time of input error Opening closing t...

Страница 24: ...n values and individual assignment to one of RA STBY and preset position value is possible z Operation Put in action when no voltage contact or open collector turns ON Event output option z Number of...

Отзывы: