- 14 -

(8)  Setting of 3 Points of External Operating Input Position Values and Individual 1 point

Three points in total of position setting and one point of individual setting (switching of output characteristics, switching of operation and 
suspension and position) are selectable.

  Setting of position values

 

1)  Setting of 3 values of position

 

  [Initial value: 0%, Setting range: 0~100%]

 

  The same setting method is applicable to 1 to 3 values of position.  When the 

 key is pressed, the display changes from the    

  position value 1 setting screen to the position value 3 setting screen successively.  Pressing the  

 key on the position value 3    

  setting screen, the 0-0 basic screen returns.  Set 3 values of position for two input points of DI1 and DI2.  DI3 is set individually.

0-70 3 value of position 

 and 

individual 

 setting 

screen

0-71 Value of position 

        1 setting screen

0-72 Value of position 

        2 setting screen

0-73 Value of position 

        3 setting screen

0-74 External input 

        3 individual setting 

        screen

To the 0-0 

basic screen

 

2)  Selection of the number of preset position values (D11 and D12)

 

  Selection is made by binary  through external operating input DI1 and DI2.

 

  Selection of preset position values (1P~7P) is as follows.

External 

operating input

Automatic

operation

Preset number of position values

The      mark signifies DI=ON.

D11

D12

OFF

OFF

OFF

OFF

  Setting of individual 1 point (DI3)

 

On the 0-74 external input 3 operating screen individual setting screen

 

Selection is possible from the following;  

: No setting(initial value), 

: Reverse characteristics, 

: Standby(waiting), 

Value of position (preset). When value of position Pr is selected the 0-74-1 value of position setting screen is called.

 

[Initial value of position: 0%, setting range: 0~100%] 

7-4.  Screen group 1 and parameter setting

There are various apparatus that have relation  to the settings in screen group 1. Please have a person who is familiar with the apparatus 
conduct the setting.

  Moving from Screen Group 0 to Screen Group 1

 When 

the   key is pressed continuously for 3 seconds, on the 0-0 basic screen, the 1-0 zero/span automatic adjustment screen 

or the 1-00 zero/span manual adjustment screen of the screen group 1 is displayed. To return to the 0-0 basic screen, press the 

 

key.

Screen group 0

0-0 basic screen

key 3 seconds

DISP

Screen group 1 

zero/span adjustment setting screen

1-0 zero/span automatic adjustment screen or 

1-00 manual adjustment screen

  Need of Zero/Span Adjustment

1)  The zero span adjustment makes adjustment when the fully opened condition(100%) or the fully closed condition(0%) is 

reached in an incorrect position.

2)  There are two types of adjustments, automatic and manual.  Connected to a control motor or the like, the instrument checks and 

adjusts the zero side and the span side of the rotating position of the motor shaft. If getting out of a position is found at the time 
maintenance/replacement of the control motor, readjustment should be made.

3)  Before using the instrument make sure to carry out zero/span adjustment.
4)  Before zero/span adjustment, make sure to confirm that all wiring has been carried out correctly. 
5)  In some cases, erroneous wiring, if any, of terminals R1 and R2 is unable to be checked.  You should be very careful to avoid 

erroneous wiring.

6)  Confirm the direction of revolutions of the motor by the use of the 

 and 

 keys in Section 7-2 Manual Operation (2).  

Once it is confirmed, change manual operation to automatic.  Zero/span adjustment is not possible in manual operation.

Use the 

 and 

 keys for switching between the 1-0 zero/span automatic screen and the 1-00 zero/span manual screen and

the 

 Key for registeration.

Содержание EM70

Страница 1: ...alog Output Type 17 9 Communication Setting 17 10 Input Range Setting 18 11 Input Filter Setting 18 12 Setting of Input Scaling Position Scaling 18 13 Position Limiter Setting 18 14 Motor Action Time...

Страница 2: ...The alert mark on the plate affixed to the instrument On the terminal nameplate affixed to the case of this instrument the alert mark is printed This is to warn you of the risk of electric shock whic...

Страница 3: ...5 16 17 OPEN 2A240VAC CLOSE COM 2A240VAC M3 M2 M1 SSR 26 TERMINAL 1 SPECIFICATION 27 28 SG SD RD SG RS 232C RS 485 Follow 3 5 Terminal Layout and 3 6 Terminal Arrangement Table and make sure to conduc...

Страница 4: ...iring is shown Particular attention should be paid to common lines and polarity INPUT DC Power supply for motor Power supply for EM70 100 240V AC 50 60Hz L N CW CW Clockwise CCW Counterclockwise Poten...

Страница 5: ...changes the display in the following order Position value input value target position value deviation value position value Display returns to the initial screen of a screen group such as 1 0 or 1 00 z...

Страница 6: ...e direction of revolution involves danger Correct the wiring if that is the case with reference to Cause of Trouble and Troubleshooting You should also confirm the positions of the control motor in th...

Страница 7: ...al input from control motor or an input error error of input signal from controller can be set Selectable from 3 types Suspension stand by action closing and opening of motor by setting its action tim...

Страница 8: ...md EXE Value of position 7 Value of position 6 0 50 0 51 0 60 0 70 Individual 3 points setting 7 values of position setting 3 values of position and individual 1 point setting Individual setting Valu...

Страница 9: ...tment Event 1 type setting Manual adjustment 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 13 1 14 1 15 1 16 1 17 1 25 1 26 1 27 1 28 1 00 1 Span side manual adjustment 1 00 2 The 1 0 zero span automatic adjustme...

Страница 10: ...ghts DISP DISP DISP DISP 0 0 Basic screen Present position value is displayed in 0 0 1 Control input value display screen Control input is displayed in 0 0 2 Target position value display screen Targe...

Страница 11: ...events allowing event set values to be set i e higher and lower limits of position and higher and lower limits of inputs as shown below 4 types of alarms Lower limit of position Higher limit of posit...

Страница 12: ...individually 7 preset position values are set for DI1 DI2 and DI3 3 preset position values are set for DI1 and DI2 and for DI3 one is selected from no rA St and Pr About DI type action and setting ra...

Страница 13: ...n to allow you to set only when Pr is selected as the value of position on the 0 51 052 and 0 53 external operating input screen 7 Setting of 7 point External Operating Input Position Value Initial va...

Страница 14: ...g range 0 100 7 4 Screen group 1 and parameter setting There are various apparatus that have relation to the settings in screen group 1 Please have a person who is familiar with the apparatus conduct...

Страница 15: ...justment screen which blinks while adjustment is going on 2 Set the motor to the zero position usually full close by the use of and keys When the key is pressed for registration the display changes to...

Страница 16: ...7 screen Event 3 type setting screen Initial value The same as event 1 Event 3 hysteresis setting screen Initial value 0 1 Setting range 0 1 5 0 The same as event 1 Event 3 stand by action setting scr...

Страница 17: ...except manual operation Communication address setting screen Initial value 1 Setting range 1 99 In case a plurality of controllers are linked for communication addresses need to be set individually to...

Страница 18: ...ling lower limit setting screen Initial value 0 Setting range 10 109 lower limit higher limit 100 0 20 80 100 Input scaling n o i t i s o P n o i t i s o P Input 100 75 15 0 0 1 0 Position scaling Inp...

Страница 19: ...ue Keylock of screen groups 1 and 2 All keylock except manual operation All keylock In case manual operation is set before setting keylock however operation by and keys is possible 1 38 Key Operation...

Страница 20: ...occur simultaneously the position error is given preference and the control loop error check is released Refer to the following formula in setting the control loop error detection time Set value of c...

Страница 21: ...iometer of control motor or for control signals Erroneous setting of output characteristic DA RA Correct wiring to potentiometer of control motor terminals 4 5 and 6 or for control signals terminals 1...

Страница 22: ...on of control loop error to a somewhat larger value Input higher limit error Control input signal exceeds higher limit 110 in HH Mismatch between input range and control input signal Problem with inpu...

Страница 23: ...3 type setting Event 3 hysteresis Event 3 stand by action Control at the time of position error Opening closing time at the time of position error Control at the time of input error Opening closing t...

Страница 24: ...n values and individual assignment to one of RA STBY and preset position value is possible z Operation Put in action when no voltage contact or open collector turns ON Event output option z Number of...

Отзывы: