- 12 -
Event output action:
Hysteresis
Set value
ON
OFF
OFF
ON
Set value
Hysteresis
Position, control input lower value event action
Position, control input upper value event action
0% side
0% side
100% side
100% side
Event standby action:
In case ON is set for event standby action, event is not output even when control input is within an event action range (an ON
range) upon applying power. Event is output only when it exceeds the event action range (i.e., enters an OFF range) and reaches
the event action range again.
(5) Selection of External Operation Input (DI) from 3 Types
External input can break in and operate by no-voltage contact or an open collector signal while the instrument is in operation.
There are 3 types of external input. Select from either individual 3 point setting, 7 point position value setting or 3 point position value
and 1 point setting.
3 type selection (Selection can be made as shown below)
0-50 Individual 3 point
setting screen
0-60 7 point position value
setting screen
0-70 3 point position value and 1 point setting
setting screen
DI1, DI2 and DI3
are set individually.
7 preset position
values are set for
DI1, DI2 and DI3.
3 preset position
values are set for
DI1 and DI2, and for
DI3, one is selected
from no, rA, St and
Pr.
About DI (type, action and setting range)
Type
Code
Action
Setting range
Individual setting (3 points)
Preset positing value setting
(7 points)
Present position value setting
(3 points) and individual
one point setting
~
~
Not effective
Reversion (DI = ON RA action, DI = OFF DA action)
When DI = ON, automatic operation is suspended (standby)
Preset position value is set.
Seven preset position values are set for DI1, DI2 and DI3.
Three preset position values are set for DI1 and DI2.
Individual setting for DI3 is the same as individual setting
(3 points).
Initial value 0%
0~100%
Initial value 0%
0~100%
Initial value 0%
0~100%
1) DI input is of level setting.
2) 0.2 second or longer is necessary from the time at which DI internal contact turns ON to the time at which the input action becomes effective.
3) If reversion of DI input control characteristic and suspension of automatic operation are selected and the selection of DI input is released while the
action is being executed with DI=ON, the action status remains unchanged.
4) In case the same selection is made for DI1, DI2 and DI3, the action is carried out in the order of DI1>DI2>DI3.