2. Introduction

This instrument, connected to a control motor to rotate the motor 
shaft, is capable of adjusting opening/closing of valves and the 
like.  Event output, analog output and communication functions 
are included as options.

2-1.    Check before Use

This product has been fully inspected for quality assurance prior 
to shipment. Nevertheless, you are requested to make sure that 
there is no error, damage or shortage of delivered items by 
checking the model codes and the external view of the product 
and the number of accessories.

Confirmation of Model Codes
Check the model codes affixed to the case of the product 
to ascertain if the respective codes designate what was 
specified when you ordered it, referring to the following 
code table:
Example of model codes:

E M 7 0 — 4

1

Y — 0

1. Series

EM70

2. Input

4:  Current 4~20mA, 0~20mA DC
6:  Voltage 1~5V, 0~5V, 0~10V DC

3. Output type

Y:  Contact 240V AC 2A with CR absober

R:  Contact 240V AC 2A withnot CR absober 

S:  Combination of SSR and contact 240V AC 2A

4. Event output

0:  Without
1:  Contact output

5. Analog output

0:  Without
4:  4~20mA DC

6. Square root 
  extraction

0:  Without
1:  With function

7. Communication

0:  Without
5:  RS-485
7:  RS-232C

8. Remarks

0:  Without
9:  With

0 0 0 0

2 3

4 5 6 7 8

Accessories
This instruction manual............................................. 1 copy
The Communication instruction manual................... 1 copy
(when the optional communication function is added)

Note:

 

 

s

e

i

r

o

s

s

e

c

c

a

 

f

o

 

e

g

a

t

r

o

h

s

 ,

t

c

u

d

o

r

p

 

e

h

h

t

i

w

 

m

e

l

b

o

r

p

 

y

n

a

 

r

o

F

 

or request for information, please contact our 
representative.

2-2.    Handling Instruction

Do not operate the keys on the front panel with a hard or 
sharply pointed object.  Operate the keys only by softly 
touching them with fingertips.

When cleaning the instrument, wipe it softly with a dry 
cloth.  Never use solvents such as thinner.

3. Installation and Wiring

3-1.    Installation Site (environmental conditions)

This instrument should not be used in any of the places 
mentioned below. Selection of these places may result in trouble 
with the instrument, damage to it or even a fire.

Where flammable gas, corrosive gas, oil mist and particles 
that can deteriorate electrical insulation are generated or 
abundant.

Where the temperature is below  10  or above 50 .

Where the relative humidity is above 90% RH or below 
the dew point.

Where highly intense vibration or impact is generated or 
transferred.

Near high voltage power lines or where inductive 
interference can affect the operation of the instrument.

 

To avoid damage to connected equipment, facilities or the EM70 
itself due to a fault of the product, safety measures must be taken 
before usage, such as the installation of a fuse, an overheating 
protection device or the like. No warranty is valid in the case of an 
accident arising from the use of this product without such safety 
measures having been undertaken.

• The alert mark     on the plate affixed to the instrument:
  On the terminal nameplate affixed to the case of this instrument, the 

alert mark     is printed. This is to warn you of the risk of electric 
shock which may result if the terminal is touched while being 
energized.

• As a means to turn the power off, a switch or a breaker should be 

installed in the external power circuit to be connected to the power 
terminal of the instrument. Fix the switch or the breaker adjacently 
to the instrument in a position which allows it to be operated with 
ease, with an indication that it is a means of turning the power off. 
Use a switch or a breaker which meets IEC60947 requirements.

• Fuse: Since the instrument does not have a built-in fuse, do not 

forget to install a fuse in the power circuit to be connected to the 
power terminal.

  Fuse rating/characteristics: 250 VAC 0.5 A/medium lagged or 

lagged type.

  Use a fuse which meets IEC60127 requirements.
• Voltage/current of a load to be connected to the output terminal and 

the alarm terminal should be within a rated range. Otherwise, the 
temperature will rise to reduce the life of the product and/or to 
result in problems with the product.

  For rated voltage/current, see 10. Specifications.
  The output terminal should be connected with a device which meets 

IEC61010 requirements.

• A voltage/current different from that of the input specification 

should not be applied to the input terminal. It may reduce the life of 
the product and/or result in problems with the product.

  For rated voltage/current, see 10. Specifications.
  In the case of voltage or current input, the input terminal should be 

connected to a device which meets IEC61010 requirements.

  The instrument is provided with a draft hole for heat discharge.  

Take care to prevent metal and other foreign matter from entering 
this hole. Failure to do so may result in trouble with the instrument 
or may even cause a fire.

• Do not block the draft hole or allow dust or the like to stick it. 

A rise in temperature or insulation failure may result in a reduction 
of the life of the product and/or problems with it or may cause a 
fire.

  For spaces between installed instruments, refer to 3-4.
  External Dimensions and Panel Cutout.
• It should be noted that repeated tolerance tests against voltage, 

noise, surge, etc. may lead to deterioration of the instrument.

• Users are prohibited from remodeling the product or abnormal use 

thereof.

• It takes 30minutes to display the correct temperature after applying 

power to the digital controller.(Therefore, turn the power on more 
than 30 minutes prior to the operation.)

• To ensure safety and maintain the functions of this device, do not 

disassemble this device. If this device must be disassembled for 
replacement or repair, contact your dealer.

• This device is designed for mounting on the panel. Only the device 

mounted on the front of the panel facing outward is of protection 
class of IP66. Do not use for the device not facing outward or in 
environment where water or solids in excess of IEC60529 may get 
inside.

Содержание EM70

Страница 1: ...alog Output Type 17 9 Communication Setting 17 10 Input Range Setting 18 11 Input Filter Setting 18 12 Setting of Input Scaling Position Scaling 18 13 Position Limiter Setting 18 14 Motor Action Time...

Страница 2: ...The alert mark on the plate affixed to the instrument On the terminal nameplate affixed to the case of this instrument the alert mark is printed This is to warn you of the risk of electric shock whic...

Страница 3: ...5 16 17 OPEN 2A240VAC CLOSE COM 2A240VAC M3 M2 M1 SSR 26 TERMINAL 1 SPECIFICATION 27 28 SG SD RD SG RS 232C RS 485 Follow 3 5 Terminal Layout and 3 6 Terminal Arrangement Table and make sure to conduc...

Страница 4: ...iring is shown Particular attention should be paid to common lines and polarity INPUT DC Power supply for motor Power supply for EM70 100 240V AC 50 60Hz L N CW CW Clockwise CCW Counterclockwise Poten...

Страница 5: ...changes the display in the following order Position value input value target position value deviation value position value Display returns to the initial screen of a screen group such as 1 0 or 1 00 z...

Страница 6: ...e direction of revolution involves danger Correct the wiring if that is the case with reference to Cause of Trouble and Troubleshooting You should also confirm the positions of the control motor in th...

Страница 7: ...al input from control motor or an input error error of input signal from controller can be set Selectable from 3 types Suspension stand by action closing and opening of motor by setting its action tim...

Страница 8: ...md EXE Value of position 7 Value of position 6 0 50 0 51 0 60 0 70 Individual 3 points setting 7 values of position setting 3 values of position and individual 1 point setting Individual setting Valu...

Страница 9: ...tment Event 1 type setting Manual adjustment 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 13 1 14 1 15 1 16 1 17 1 25 1 26 1 27 1 28 1 00 1 Span side manual adjustment 1 00 2 The 1 0 zero span automatic adjustme...

Страница 10: ...ghts DISP DISP DISP DISP 0 0 Basic screen Present position value is displayed in 0 0 1 Control input value display screen Control input is displayed in 0 0 2 Target position value display screen Targe...

Страница 11: ...events allowing event set values to be set i e higher and lower limits of position and higher and lower limits of inputs as shown below 4 types of alarms Lower limit of position Higher limit of posit...

Страница 12: ...individually 7 preset position values are set for DI1 DI2 and DI3 3 preset position values are set for DI1 and DI2 and for DI3 one is selected from no rA St and Pr About DI type action and setting ra...

Страница 13: ...n to allow you to set only when Pr is selected as the value of position on the 0 51 052 and 0 53 external operating input screen 7 Setting of 7 point External Operating Input Position Value Initial va...

Страница 14: ...g range 0 100 7 4 Screen group 1 and parameter setting There are various apparatus that have relation to the settings in screen group 1 Please have a person who is familiar with the apparatus conduct...

Страница 15: ...justment screen which blinks while adjustment is going on 2 Set the motor to the zero position usually full close by the use of and keys When the key is pressed for registration the display changes to...

Страница 16: ...7 screen Event 3 type setting screen Initial value The same as event 1 Event 3 hysteresis setting screen Initial value 0 1 Setting range 0 1 5 0 The same as event 1 Event 3 stand by action setting scr...

Страница 17: ...except manual operation Communication address setting screen Initial value 1 Setting range 1 99 In case a plurality of controllers are linked for communication addresses need to be set individually to...

Страница 18: ...ling lower limit setting screen Initial value 0 Setting range 10 109 lower limit higher limit 100 0 20 80 100 Input scaling n o i t i s o P n o i t i s o P Input 100 75 15 0 0 1 0 Position scaling Inp...

Страница 19: ...ue Keylock of screen groups 1 and 2 All keylock except manual operation All keylock In case manual operation is set before setting keylock however operation by and keys is possible 1 38 Key Operation...

Страница 20: ...occur simultaneously the position error is given preference and the control loop error check is released Refer to the following formula in setting the control loop error detection time Set value of c...

Страница 21: ...iometer of control motor or for control signals Erroneous setting of output characteristic DA RA Correct wiring to potentiometer of control motor terminals 4 5 and 6 or for control signals terminals 1...

Страница 22: ...on of control loop error to a somewhat larger value Input higher limit error Control input signal exceeds higher limit 110 in HH Mismatch between input range and control input signal Problem with inpu...

Страница 23: ...3 type setting Event 3 hysteresis Event 3 stand by action Control at the time of position error Opening closing time at the time of position error Control at the time of input error Opening closing t...

Страница 24: ...n values and individual assignment to one of RA STBY and preset position value is possible z Operation Put in action when no voltage contact or open collector turns ON Event output option z Number of...

Отзывы: