- 18 -

to the 1-29 screen

1-27

1-24

1-28

1-26

1-25

Communication delay time setting screen

Initial value: 20
Setting range: 0~100

 A delay time from receiving a communication

command to carrying out transmission is set.

Delay time = Set value of communication 
delay time 

×

0.25 msec.

(10) Input Range Setting

Input range setting screen

Initial value:
           in the case of current input
           in the case of voltage input
Select one from the following types of current 
input.

: 4~20mA (initial value)
: 0~20mA 

Select one from the following types of voltage 
input.

: 0~10V (initial value)
:  0~5V
:  1~5V

(11) Input Filter Setting

Input filter setting screen

Initial value: 0 second
Setting range: 0~99 seconds

A time constant of primary delay filter is set.

The influence of noise contained in control 
input signal is mitigated and control is 
stabilized.

(12) Setting of Input Scaling/Position Scaling

Screen for setting input scaling/degree of 

opening scaling

Initial value:
Select from the following shown on the screen:
   : Input scaling (initial value)
   : Scaling of degree of opening

When the setting of input scaling or scaling of 
the degree of opening is changed, lower and 
higher limit values of the scaling are initialized.

Input scaling: Higher and lower limit values 
of input are set respectively against 0% and 
100% positions.

Position scaling: Higher and lower limit 
positions are set respectively against 0% and 
100% inputs.

Scaling lower limit setting screen

Initial value: 0%
Setting range: -10~109%
(lower limit < higher limit)

100%

0%

20%

80% 100%

Input scaling

n

o

it

i

s

o

P

n

o

it

i

s

o

P

Input

100%

75%

15%

%

0

0

1

%

0

Position scaling

Input

Scaling higher limit setting screen

Initial value: 100%
Setting range: 

9~110%

(lower limit < higher limit)

(13) Position Limiter Setting

Screen for setting lower limit value of 

position limiter

Initial value: 0%
Setting range: 0~99%
(lower limit < higher limit)

Screen for setting higher limit 

Motor speed adjustment “1G” setting screen
Initial value: 100%
Setting range: 10

100%

When voltage / current input (automatic oper-
ation) is selected , motor speed adjustment is 
carried out with the parameter “1G”.

side value of position limiter

Initial value: 100%
Setting range: 1~100%
 (lower limit < higher limit)

Position limiter is effective except during manual 
operation and position abnormality.
Preset values of position through external 
operating input and preset values of position at 
the time of input error also become effective.

(14) Motor Action Time Setting

Motor speed adjustment setting screen

Initial value: 100%
Setting range: 10~100%

The motor speed is adjustable when SSR 
output is selected.

When the motor speed is adjusted, control is 
carried out with a set cycle time (initial 
value: 500 msec.) as one cycle.

¥  In the case of 10% selected on the motor

speed adjustment screen:

(15) Setting of Square Root Extraction Function

1-31

1-30

1-29

Motor ON

OFF

450ms

50ms

500ms

¥  Motor action time set at 50%

Motor ON

OFF

250ms

250ms

500ms

to the 1-33 screen

Higher limit

Lower limit

80%

20%

20%

0%

80%

Position

Input

1-32

Содержание EM70

Страница 1: ...alog Output Type 17 9 Communication Setting 17 10 Input Range Setting 18 11 Input Filter Setting 18 12 Setting of Input Scaling Position Scaling 18 13 Position Limiter Setting 18 14 Motor Action Time...

Страница 2: ...The alert mark on the plate affixed to the instrument On the terminal nameplate affixed to the case of this instrument the alert mark is printed This is to warn you of the risk of electric shock whic...

Страница 3: ...5 16 17 OPEN 2A240VAC CLOSE COM 2A240VAC M3 M2 M1 SSR 26 TERMINAL 1 SPECIFICATION 27 28 SG SD RD SG RS 232C RS 485 Follow 3 5 Terminal Layout and 3 6 Terminal Arrangement Table and make sure to conduc...

Страница 4: ...iring is shown Particular attention should be paid to common lines and polarity INPUT DC Power supply for motor Power supply for EM70 100 240V AC 50 60Hz L N CW CW Clockwise CCW Counterclockwise Poten...

Страница 5: ...changes the display in the following order Position value input value target position value deviation value position value Display returns to the initial screen of a screen group such as 1 0 or 1 00 z...

Страница 6: ...e direction of revolution involves danger Correct the wiring if that is the case with reference to Cause of Trouble and Troubleshooting You should also confirm the positions of the control motor in th...

Страница 7: ...al input from control motor or an input error error of input signal from controller can be set Selectable from 3 types Suspension stand by action closing and opening of motor by setting its action tim...

Страница 8: ...md EXE Value of position 7 Value of position 6 0 50 0 51 0 60 0 70 Individual 3 points setting 7 values of position setting 3 values of position and individual 1 point setting Individual setting Valu...

Страница 9: ...tment Event 1 type setting Manual adjustment 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 13 1 14 1 15 1 16 1 17 1 25 1 26 1 27 1 28 1 00 1 Span side manual adjustment 1 00 2 The 1 0 zero span automatic adjustme...

Страница 10: ...ghts DISP DISP DISP DISP 0 0 Basic screen Present position value is displayed in 0 0 1 Control input value display screen Control input is displayed in 0 0 2 Target position value display screen Targe...

Страница 11: ...events allowing event set values to be set i e higher and lower limits of position and higher and lower limits of inputs as shown below 4 types of alarms Lower limit of position Higher limit of posit...

Страница 12: ...individually 7 preset position values are set for DI1 DI2 and DI3 3 preset position values are set for DI1 and DI2 and for DI3 one is selected from no rA St and Pr About DI type action and setting ra...

Страница 13: ...n to allow you to set only when Pr is selected as the value of position on the 0 51 052 and 0 53 external operating input screen 7 Setting of 7 point External Operating Input Position Value Initial va...

Страница 14: ...g range 0 100 7 4 Screen group 1 and parameter setting There are various apparatus that have relation to the settings in screen group 1 Please have a person who is familiar with the apparatus conduct...

Страница 15: ...justment screen which blinks while adjustment is going on 2 Set the motor to the zero position usually full close by the use of and keys When the key is pressed for registration the display changes to...

Страница 16: ...7 screen Event 3 type setting screen Initial value The same as event 1 Event 3 hysteresis setting screen Initial value 0 1 Setting range 0 1 5 0 The same as event 1 Event 3 stand by action setting scr...

Страница 17: ...except manual operation Communication address setting screen Initial value 1 Setting range 1 99 In case a plurality of controllers are linked for communication addresses need to be set individually to...

Страница 18: ...ling lower limit setting screen Initial value 0 Setting range 10 109 lower limit higher limit 100 0 20 80 100 Input scaling n o i t i s o P n o i t i s o P Input 100 75 15 0 0 1 0 Position scaling Inp...

Страница 19: ...ue Keylock of screen groups 1 and 2 All keylock except manual operation All keylock In case manual operation is set before setting keylock however operation by and keys is possible 1 38 Key Operation...

Страница 20: ...occur simultaneously the position error is given preference and the control loop error check is released Refer to the following formula in setting the control loop error detection time Set value of c...

Страница 21: ...iometer of control motor or for control signals Erroneous setting of output characteristic DA RA Correct wiring to potentiometer of control motor terminals 4 5 and 6 or for control signals terminals 1...

Страница 22: ...on of control loop error to a somewhat larger value Input higher limit error Control input signal exceeds higher limit 110 in HH Mismatch between input range and control input signal Problem with inpu...

Страница 23: ...3 type setting Event 3 hysteresis Event 3 stand by action Control at the time of position error Opening closing time at the time of position error Control at the time of input error Opening closing t...

Страница 24: ...n values and individual assignment to one of RA STBY and preset position value is possible z Operation Put in action when no voltage contact or open collector turns ON Event output option z Number of...

Отзывы: