- 18 -
to the 1-29 screen
1-27
1-24
1-28
1-26
1-25
Communication delay time setting screen
Initial value: 20
Setting range: 0~100
A delay time from receiving a communication
command to carrying out transmission is set.
Delay time = Set value of communication
delay time
×
0.25 msec.
(10) Input Range Setting
Input range setting screen
Initial value:
in the case of current input
in the case of voltage input
Select one from the following types of current
input.
: 4~20mA (initial value)
: 0~20mA
Select one from the following types of voltage
input.
: 0~10V (initial value)
: 0~5V
: 1~5V
(11) Input Filter Setting
Input filter setting screen
Initial value: 0 second
Setting range: 0~99 seconds
A time constant of primary delay filter is set.
The influence of noise contained in control
input signal is mitigated and control is
stabilized.
(12) Setting of Input Scaling/Position Scaling
Screen for setting input scaling/degree of
opening scaling
Initial value:
Select from the following shown on the screen:
: Input scaling (initial value)
: Scaling of degree of opening
When the setting of input scaling or scaling of
the degree of opening is changed, lower and
higher limit values of the scaling are initialized.
Input scaling: Higher and lower limit values
of input are set respectively against 0% and
100% positions.
Position scaling: Higher and lower limit
positions are set respectively against 0% and
100% inputs.
Scaling lower limit setting screen
Initial value: 0%
Setting range: -10~109%
(lower limit < higher limit)
100%
0%
20%
80% 100%
Input scaling
n
o
it
i
s
o
P
n
o
it
i
s
o
P
Input
100%
75%
15%
%
0
0
1
%
0
Position scaling
Input
Scaling higher limit setting screen
Initial value: 100%
Setting range:
−
9~110%
(lower limit < higher limit)
(13) Position Limiter Setting
Screen for setting lower limit value of
position limiter
Initial value: 0%
Setting range: 0~99%
(lower limit < higher limit)
Screen for setting higher limit
Motor speed adjustment “1G” setting screen
Initial value: 100%
Setting range: 10
―
100%
When voltage / current input (automatic oper-
ation) is selected , motor speed adjustment is
carried out with the parameter “1G”.
side value of position limiter
Initial value: 100%
Setting range: 1~100%
(lower limit < higher limit)
Position limiter is effective except during manual
operation and position abnormality.
Preset values of position through external
operating input and preset values of position at
the time of input error also become effective.
(14) Motor Action Time Setting
Motor speed adjustment setting screen
Initial value: 100%
Setting range: 10~100%
The motor speed is adjustable when SSR
output is selected.
When the motor speed is adjusted, control is
carried out with a set cycle time (initial
value: 500 msec.) as one cycle.
¥ In the case of 10% selected on the motor
speed adjustment screen:
(15) Setting of Square Root Extraction Function
1-31
1-30
1-29
Motor ON
OFF
450ms
50ms
500ms
¥ Motor action time set at 50%
Motor ON
OFF
250ms
250ms
500ms
to the 1-33 screen
Higher limit
Lower limit
80%
20%
20%
0%
80%
Position
Input
1-32