35
Figure 4-34 Output result
If it is indicated that the linkage condition is true, two modules (module 1 and module 2) will
be requested for action. The two modules control fire pumps.
In the linkage interface, only the module address number can be
selected, the equipment controlled by the module shall be set at the
detector/module setup form.
Step 3: confirm
Press Confirm button and the system will save the linkage condition and exit the linkage
setup interface. Press Add, Next or Prev to switch to another linkage condition setup interface to
proceed. At switching over, the system will save the linkage conditions set just now.
The setup of a linage relation is completed after conducting the above 4 steps. The
following section will present respective diagrams.
The operation of "delay" drop-down box is as shown in the following figure:
Figure 4-32 Delay selection
There are 8 time selections for delay: 0s, 5s, 10s, 30s, 60s, 90s, 120s and 150s.
Selection of input type, as follows: