34
Each page (i.e. display of the entire screen) corresponds to a linkage condition. The setup
flow of a linkage condition is as follows:
Step 1: condition setting
Four buttons (Prev, Next, Add and Del) and a text input box are set above the condition
setting area, which are used for inquiring, adding or deleting linkage conditions.
Adding a linkage condition: click on Add button
Deleting a linkage condition: click on Del button
Viewing or editing the linkage condition on the previous page: click on Prev
Viewing or editing the linkage condition on the next page: click on Next
Viewing or editing a certain linkage condition: enter serial number of the linkage condition
into the text box before "Pg", enter or click on To button
The system will display another linkage condition when any of the above operations is
carried out. "Cond. 1/3" at top left corner of the display means currently there are 3 system
linkage conditions and the first one is displayed at the moment. If the linkage conditions are
large in number, enter into the page number to skip. If the corresponding modules of a linkage
condition are multiple, the page switching may take 2-5s.
The edit area for current linkage condition is set below the condition setting area.
"Delay": select the time interval between condition satisfied and action of module;
"Reg": check the option to activate the linkage action on this page;
"Input type": composed of check box at the left side and drop-down box at the right side. The
relation between input type is "or";
"Fire QTY": the number of fires required to satisfy the conditions. For example, 01 means
the conditions are satisfied when the alarms is generated at any 1 point. The system can
achieve composite functions of multiple arbitrary alarms and the maximum composite number is
99.
Therefore, the linkage conditions in the above figure are as follows:
Step 2: select the module required to be started when conditions are satisfied
Click on a certain module in the list box and click on << button, to add this module into the
result list area. Except for "manual control panel linkage setup", a linkage condition can be used
to start multiple modules, therefore step 2 and step 3 can be repeated to add multiple output
results.
The modules started by a condition are limited in number and a condition can be used to
start 200 modules at most. If the number exceeds 200, the user must set another different
number with the same conditions, to correspond to modules with numbers exceeding 200.
Check a module in the "Result list" and click on >> button to delete the module from the
result list.
The display of result output column in the figure is as follows: