25
The 485-bus indicating panel setup panel is as follows; refer to instructions on
detector module setup for indicating panel setup of detector bus:
Figure 4
‑
13 Indicating panel setup interface 1
Find the address of 485 bus indicating panel to be registered. Click on "Registration"
column to show "
√
". Double click "Type", "Building" and "Floor" columns and select type,
building and floor in the drop-down box. Enter description information at "position description"
column.
Then press OK button to save the setup and exit; press cancel button to retain the original
setup and exit.
The following shall be set up for 485 equipment:
Type
- 485 equipment is divided into the following types:
Building indicating panel - Chinese (building indicating panel in Chinese)
Floor indicating panel - Chinese (floor indicating panel in Chinese)
Building indicating panel - digital (digital building indicating panel)
Floor indicating panel - digital (digital floor indicating panel)
The indicating panels can be divided into building indicating panel and floor indicating panel
by working mode that is a certain indicating panel can display all alarm messages of the whole
building. It expands the function of floor indicating panel (JB-FSD-982 fire indicating panel).
position description
- each indicating panel/expansion box can enter position
description information independently, as the location display at alarm. The position description
can contain 20 Chinese characters or 40 English characters.
Building and floor
- if the type of indicating panel is "building indicating panel", the
floor information can be deemed as location display information only when there is not fault
alarm of position description.
If the fire indicating panels are large in number or long in connection, it is suggested to use
the twisted-pair with large diameter and to use the shielded twisted pair for the applications with
more external disturbances.
The
The
negative
negative
wire
wire
of
of
24V
24V
power
power
supply
supply
of
of
the
the
fire-indicating
fire-indicating
panel
panel
shall
shall
be
be
connected
connected
to
to
24V
24V
negative
negative
wire
wire
of
of
the
the
control
control
unit
unit to ensure normal and reliable
communication. The joint shall be welded as much as possible. The specific wire diameter shall
be determined per the construction environment. If the indicating panels are small in number
and short in connection, the ordinary connecting line can be used.
4.1.6 EXT.-connected FIP setup
Refer to the "(4.1.5)FIP/Extender setup".
4.1.7 Power setup
The system can monitor the power supply and specify the power for the host. The power
setup interface is as follows: