8
Service
Description of status and operating displays
Operating Instructions – MOVIGEAR
®
performance
159
8.6.5
Bus-specific LEDs for PROFINET IO
"BF" LED
LED
Meaning
Measure
–
Off
The unit has detected a connection to the
PROFINET master.
–
Red
Illuminated
The connection to the PROFINET master
has failed.
The device detects no connection to the
PROFINET master (bus error).
•
Check the PROFINET connection of
the unit.
•
Check all the cables in the
PROFINET network.
The PROFINET master is not in operation.
•
Check the PROFINET master.
Faulty process data configuration.
•
Check the process data configura-
tion.
"US1" LED
LED
Meaning
Measure
Yellow
Flashing
The device is in the initialization phase.
•
Wait for initialization to be com-
pleted.
Green
Illuminated
The device works in normal operation.
–
Green
Flashing
Reserved
–
Red
Illuminated
The device has detected an internal fault.
•
Observe the instructions in the
chapter "Fault table".
25945475/EN – 04/2019