8
Service
Fault table standard
Operating Instructions – MOVIGEAR
®
performance
205
Subfault: 31.7
Description: UL temperature monitoring
Response: Output stage inhibit
Cause
Measure
Temperature model of active motor signals over-
temperature.
Check for motor overload.
Subfault: 31.8
Description: Communication timeout temperature sensor – motor 1
Response: Output stage inhibit
Cause
Measure
Communication with temperature sensor is dis-
rupted, e.g. via MOVILINK
®
.
Check the cabling.
Subfault: 31.9
Description: Temperature too low – temperature sensor – motor 1
Response: Warning with self-reset
Cause
Measure
Temperature signaled by temperature sensor of
motor 1 below -50 °C.
– Check if a KTY temperature sensor is installed
in the motor but the parameterization has been
carried out for a Pt1000 temperature sensor.
– Heat the motor.
Subfault: 31.11
Description: Temperature sensor wire break – motor 2
Response: Application stop + output stage inhibit
Cause
Measure
Connection to temperature sensor of motor 2 in-
terrupted.
Check the temperature sensor wiring.
Subfault: 31.12
Description: Temperature sensor short circuit – motor 2
Response: Application stop + output stage inhibit
Cause
Measure
Short circuit in connection with temperature
sensor of motor 2.
Check the temperature sensor wiring.
25945475/EN – 04/2019