7.0 Using an AGS
71
© 2020 Sensata Technologies
7.7
AGS Remote Status Messages
A status message may be an operational or a fault message. Access the AGS
status menu (AGS button’s
02 AGS Status
menu) to view the AGS’s current
operating status. This menu is important when determining if the AGS is
working correctly, or for troubleshooting an AGS installation.
7.7.1 AGS Remote Operational Statuses
Refer to Table 7-3 for a brief description of the possible AGS operational
statuses that may display.
Table 7-3, AGS Remote Operational Statuses
STATUS
DESCRIPTION
AC In
The inverter/charger is connected to another source such as
a grid or an alternate generator, and is not controlled by the
AGS. When
AC In
displays, the AGS is prevented or locked out
from all autostarting conditions, except for when the generator
needs to exercise—if enabled.
Lock-
out
Lockout occurs when the AGS system is automatically disabled
because the generator has been started or stopped for any
condition outside the control of the AGS.
Note:
When a Lockout status occurs, the AGS: 01 AGS Control menu
automatically changes from Enable (or Enable w/QT) to OFF. For
assistance in clearing or disabling this status, refer to Section 7.8.2.
Note:
This lockout is a requirement for RV installations—per RVIA. For
installations where the requirement to automatically disable the AGS
system is not needed, the AGS mode can be changed to “Other”. For
information, refer to Section 7.8.2 and on the AGS Mode under the AGS:
08 AGS TECH menu on page 74.
Manual
Run
Generator was started manually from a switch directly
connected to the generator, and the
AGS Mode
=
Other
(if the
AGS Mode=RV
, a Lockout fault displays instead).
Note:
The AGS determines that the gen has been manually turned on
if the gen run sense voltage is detected on Terminal #2 of the AGS’s
8-port terminal. However, if the Gen Type DIP switch is set to “2-Wire
Standby”—which does not require the gen run sense voltage—manually
turning the gen on displays “AC In” rather than “Manual Run”.
No
Comm
The AGS is not communicating with the inverter/remote. This is
a normal status if there is no AGS (Network version) connected
in the system. If an AGS is installed, then refer to Section 7.8.2
“Resolving Operational Statuses”.
Off
The
AGS: 01 AGS Control
menu is set to
OFF
. This setting will
not allow the AGS to autostart the generator.
Quiet
Time
The ME-AGS-N has entered Quiet Time per the
AGS: 07 Quiet
Time
setting.
Note:
The generator will not autostart during Quiet Time
.
Ready
The
AGS: 01 AGS Control
menu is set to
Enable
or
Enable w/
QT
, and the AGS is ready to automatically start the generator
based on the AGS button’s active autostart settings.