3.0 Setup
11
© 2020 Sensata Technologies
Button
FEATURES/SETTINGS
Inverter
Level
Required
Default
Setting
Menu
Heading
Menu
Item
Selections/
Adjustments Range
SETUP
01 Search
Watts
Search= OFF, 5 - 50W
≥
Level 1
5W
02 Low Batt
CutOut
LBCO=
9.0 - 12.2 VDC
*
≥
Level 1
10.0 VDC
9.0 - 13.0 VDC*
≥
Level 5
03 Absorb
Time
Absorb
Hrs= 0.1 - 25.5 Hrs
≥
Level 4[4]
1.5 Hrs
04 Battery
Type
BatType=
Gel, Flooded, AGM1, AGM2
≥
Level 1
Flooded
Cus-
tom
[2]
Absorb =
(12.0 - 16.0V)
*
≥
Level 3
14.4V
Float =
(12.0 - 16.0V)
*
13.2V
Equalize =
(12.0 - 16.0V)
*
15.6V
CC/
CV
Max Amps =
(OFF, 20 - 990A)
≥
Level 3
200A
Chg Volts =
(12.0 - 16.0V)
*
13.8V
EndChg = (Time, DC
Amps, Hold VDC)
Time
EndChg = Time
DoneTime =
(0.1 - 25.5 Hrs)
≥
Level 4
[4]
1.5Hrs
MaxTime = (OFF,
0.1-25.5)
12.0Hrs
Recharge =
(12.0-16.0V)
*
12.0V
EndChg= DC Amps
DoneAmps =
(0 - 250ADC)
≥
Level 4
20ADC
MaxTime = (OFF,
0.1-25.5)
12.0Hrs
Recharge =
(12.0-16.0V)
*
12.0V
Hold VDC
≥
Level 1
14.6V
LFP
≥
Level 5
05 Charge
Rate
Max
Charge=
0 - 100%
≥
Level 3
80%
10 - 100%
≥
Level 2
06 VAC
Dropout
Dropout=
US Models: 60 - 100 VAC,
UPS Mode
≥
Level 1
80 VAC
Export Models: 110 - 190
VAC, UPS Mode
≥
Level 1
150 VAC
Drop-
out2=
US Models: 60 - 100 VAC,
UPS Mode
Dual-source
Models only
80 VAC