3.0 Setup
9
© 2020 Sensata Technologies
3.2
Remote Feature to Inverter Compatibility
The ME-RC has many settings and is designed to work with the standard
features in your Magnum inverter—and/or other Magnum devices (i.e., ME-
AGS-N or ME-BMK). The ME-RC communicates with your inverter to allow
the set up and enabling of these standard features. However, when the ME-
RC is released with new software, some of the features and functionality in
the remote may not be available in an inverter or networked accessory that
has an earlier software level. In this case, the setting is not recognized and
will not function. Use the steps below to help you determine which ME-RC
(Revision 2.9) menus/features are compatible with your inverter.
1. Obtain your inverter’s software revision.
Note:
To view the inverter’s software revision level, go to the TECH
menu on your remote and access the Revisions menu.
2. Go to the Magnum Remote Compatibility page at www.SensataPower.com
to determine your inverter’s compatibility level (L1, L2, L3, L4, or L5).
3. Use Table 3-1 to determine which ME-RC features/settings you want to
use, and what inverter compatibility level is required (see the “Inverter
Level Required” column in Table 3-1).
4. If your inverter compatibility level is the same or greater than the level
required, your inverter can support the setting/feature you want.
Info:
The ME-RC compatibility matrix below is also available at www.
SensataPower.com to download/print as a single page document.
Table 3-1, ME-RC (Revision 2.9) Compatibility Matrix
Button
FEATURES/SETTINGS
Inverter
Level
Required
Default
Setting
Menu
Heading
Menu
Item
Selections/
Adjustments Range
SHORE
Shore Max
5 - 60A
≥
Level 1 [1]
30A**
Shore Max2
5 - 60A
Dual Source
Inverter Models
30A**
AGS
01 AGS
Control
AGS= OFF, Enable, Test, En-
able w/QT (Set Time)
≥
Level 1
OFF
**
02 AGS
Status
AGS: Read only display
≥
Level 1
Read Only
03 Run
Time Hour
Run
Time= 0.5 - 25.5 Hours
≥
Level 1
2.0 Hrs
04 Start
Temp F
Start
Temp=
OFF, Ext Input, 65 -
95F
≥
Level 1
OFF
05 Start
Volts
Start
VDC= OFF, 10.0 - 12.2
*
≥
Level 1
11.0
06 Set
Time
Hour= 01:xxx-12:xxx
≥
Level 1
12:00A
Minute= xx:00x-xx:59x
AM-PM= xx:xxA-xx:xxP
07 Quiet
Time
Quiet=
OFF,
9PM- (7AM/8AM/9AM),
(10PM/11PM) - 8AM
≥
Level 1
OFF