7.0 Using an AGS
© 2020 Sensata Technologies
68
To manually stop the generator (only if autostarted by AGS):
1. Press the AGS button. The
01 AGS Control
menu displays.
2. Press the SELECT knob. The current gen control setting displays with an
arrow to the right.
3. Turn the SELECT knob to the
AGS = OFF
setting.
4. Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen and the display returns to the
01 AGS
Control
menu. The generator should stop at this time.
If the generator does not stop as expected, refer to your AGS Owner’s
Manual.
Autostop Conditions
•
03 Run Time Hour (page 62)
•
07 Quiet Time (page 64)
Autostart Conditions
•
04 Start Temp F (pages 62-63)
•
05 Start Volts (pages 63-64)
7.4
Enabling the AGS using the ME-RC
Before the AGS can begin operating/monitoring for an autostart condition
(using the active AGS settings in the ME-RC remote), it must be enabled.
To enable the AGS:
1. Press the AGS button. The
01 AGS Control
menu displays.
2. Press the SELECT knob. The current gen control setting displays with an
arrow to the right.
3. Turn the SELECT knob to the
AGS = Enable
setting (or to
Enable w/QT
).
4. Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen.
The AGS is now ready to automatically start/stop the generator once an
autostart condition is satis
fi
ed.
Note:
If power is lost to the remote, the AGS control setting returns to the
default OFF setting. Once power is restored, you must enable the AGS again.
Note:
Despite enabling the AGS, you must check the AGS’s current status
and ensure the status displays as “Ready”.
7.5
Starting/Stopping the Generator using ME-RC
The generator can be manually stopped, as well as autostarted/autostopped
using the available settings from your ME-RC.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the following
autostart/autostop conditions must be pre-set:
Press the ME-RC’s TECH button, and then rotate and press the SELECT knob
to access the following menus:
TECH: 01 Temperatures Menu (AGS)
This read-only menu displays the ambient temperature reading of the AGS’s
temperature sensor (if installed).
Note:
This AGS temperature meter displays the same info as the AGS: 08
AGS TECH menu’s Temp meter (see info for this meter on previous page).
TECH: 02 Revisions Menu (AGS)
This read-only menu displays the
fi
rmware revision level of the AGS module
that is installed and networked.