Fan Motor Removal
Important!
Always isolate the water and
electricity supply to the cooler before
performing motor maintenance work on
coolers
.
The Fan/Motor assembly in small cabinet
EXQ/EZQ/EXS coolers is removed via the
air outlet located at the bottom of the scroll
assembly. This requires the scroll assembly
to be disconnected from the tank. Remove
the cooler lid to provide the best access. For
safety reasons, we recommend to remove the
cooler’s scroll assembly from the roof before
performing the motor change-over. This would
require 2 persons.
1. Remove pad frames.
2. Unplug motor cables (2) from Terminal Box
3. Remove Dust Cap (rotate anti-clockwise
4. Remove screw from Shaft end).
5. Cut cable ties & undo twist tie holding cables
to scroll.
ILL187-K
1
3
2
2
5
4
3
ILL1472-C
BREEZAIR EXQ / EZQ / EXS
EVAPORATIVE COOLER
cont
12. Remove motor from shaft / scroll centre
assembly.