SEELEY INTERNATIONAL
- SERVICE GUIDE
|
35
BRAEMAR LCQI EVAPORATIVE
COOLER
cont
• Debris interfering with water sensor probes.
• Probes not clipped onto mounting brackets
correctly.
• Check cooler is level and water drains quickly.
FAULT CODE 07 (7 Red Flashes)
Motor error
WARNING: Motor/Fan could re-start without
warning as the controller attempts to re-
start the motor within 30 seconds of initially
failing this Fault Code.
•
Ensure the motor power cable is fitted correctly to
the control electronics.
•
Ensure the motor communication cable is fitted
correctly to the control electronics
•
FAULT CODE 08 (8 Red Flashes)
Supply Voltage error
WARNING: Motor/Fan could re-start without
warning as the cooler will re-start should
the voltage return to normal.
• Fan shuts down when supply voltage drops below
93V.
SALINITY LED
The Red LED (right-hand LED) is used to
indicate the condition of water salinity and
configuration of the water management
system. Parameters are set by MagIQtouch or
MagIQcool wall controllers. Refer to pages 17
or 21 of the service manual.
Salinity LED Indication for evaporative coolers
fitted with drain valves.
Sal Flash
Indicates
OFF
Not Applicable
1 Flash
WaterMiser
®
salinity is below the
set point.
2 Flash
WaterMiser
®
salinity is above the
set point.
3 Flash
The Salinity Control Method is set
for Timed Drain
4 Flash
Bleed Tray - No Drain Valve.
5 Flash
Thermostatic Control (no Water)
operation set.
Continuously
on
(When probes
immersed in
water)
Water not detected. The probes
are immersed in water but are
open circuit, or measured salinity
is less than 20µs/cm (the water
has very little salt content).
Continuously
on
(No water in
tank)
WaterMiser
®
/ Drain Valve option
is active
ILL2130-A
COMPONENT COMPATIBILITY WITH
OTHER SEELEY COOLERS
Note!
Drain Valves, Water Management
Probes and Solenoids used in EXQ/LCQ/BMQ/
CPQ products are different to those used in the
LCQI models and are NOT interchangeable.
Refer to the table shown on Page page 38
for correct part numbers for LCQI Spares
items.