54
|
MAGIQTOUCH & MAGIQCOOL MODELS
TECHNICAL BULLETIN:
A16/08 WATER DISTRIBUTION HOSE CONNECTIONS
IMPORTANT SAFETY:
When any side panels
are removed, always test EVAP coolers with
the pump disconnected or in ventilation mode,
as wet surfaces can create a safety hazard!
Also, care must always be taken when working
near or around moving parts.
INSTALLATION REMINDER
In order to avoid unnecessary inconvenience
to our Customers, we ask that during
commissioning of a Breezair Icon Series
Evaporative cooler, the following checks are
carried out:
•
All water spreaders are correctly in place
and secured to lid of cooler with screw.
•
Check water distribution hoses are firmly
fitted to spigots on the spreaders.
•
Check water distribution hoses are firmly
fitted to 4 way distributor from the pump.
•
Ensure pads are correctly fitted into
frames and washers that hold pads on
pad pins are firm.
•
Check level of Cooler in all directions,
taking care to ensure that it does not
lean backwards. If so, the unit must be
levelled.
•
Check all Inlet water supply connections
have no leaks.
•
Always fill the unit with water and initiate
a drain to ensure all drain fittings and
pipes have no leaks. The tank can be
manually drained by pressing the remote
control drain button (Horizon), or with a
wall control (Harmony) in the “OFF” state,
by pressing both the up and down buttons
simultaneously until the letters “dr” appear
on the screen.
•
Check the water will fluently drain
from the tank without air locking or
obstructions. Also, check there are no
leaks from drain hose joints.
•
Drain water must not discharge onto the
roof surface.
•
Dropper and all roof penetrations are
correctly flashed and sealed.
•
As a final check, with all side panels in
place and the unit running for a short
period in cooling mode, ensure all 4 pads
have even water saturation and there are
no visible water leaks.
•
The owner is instructed on how to isolate
the water to the system in case of an
emergency.
We thank you in advance for your co-operation
in this matter
Subject: Water Distribution Hose Connections
Bulletin Number: A16/08
Region: Australia
Author: Technical Support 1300 650 399
Date: 21/11/2008
TECHNICAL BULLETIN