40
|
MAGIQTOUCH & MAGIQCOOL MODELS
WATER COMPONENT TESTING
To test water components using the touch
controller, use the Service Operating Screen
which can be accessed from the SERVICE
menu in SETTINGS.
After entering the Service pin code (7378),
select the evaporative cooler from the
displayed list.
Scroll down and select the “Service Operating
Screen” feature.
This will open a screen which allows direct
control of the fan and all water components for
testing and troubleshooting purposes.
ILL1824-A
ILL1825-A
ILL1826-A
ILL1520-B
• Clean the metal probes
• Set the multimeter to ohms mode
• Pin 1 - Blue wire = approx. 0 (zero) ohms
• Pin 2 - Black wire = approx. 0 (zero) ohms
• * Pin 3 - Brown wire = approx 0 (zero) ohms
(3 prong probes only)
# A reading of 5 ohms or greater indicates
faulty probes.
* The brown wire (Pin 3) is not connected on 2
prong probes.
If the probe continues to fault, check between
the contacts to ensure there are no short
circuits.
PIN 1 (BLUE)
PIN 2 (BLACK)
PIN 3 (BROWN)
PIN 4 (EMPTY)
0.00
+
-
ILL1520-A
Pin 1
Pin 2
Pin 3
Component Status Resulting Action
Pump
ON
Tornado pump active,
water pumping over pads
OFF
Pump off
Solenoid
ON
Solenoid open
(water filing tank)
OFF
Solenoid closed
Drain
ON
Drain closed (energised)
OFF
Drain open
WATER SALINITY PROBE TESTING
The pump, solenoid and drain valve can be
operated tested from the Service Operating
Screen. Each component has a corresponding
ON/OFF slide button located under the “Water
Management” heading.
Note!
It is recommended that each component
be operated one at a time to avoid problems.
Care should also be taken to observe the
water level in the tank to avoid overflow or
running dry.
WATER SALINITY PROBE TESTING