8.0 TROUBLE SHOOTING GUIDE
8.1 ELECTRICAL TROUBLE SHOOTING-MOTOR
CAUTION: ALL ELECTRICAL WORK PERFORMED ON THE 9012 IRONWORKER SHALL
BE DONE BY A QUALIFIED ELECTRICIAN.
A.
MOTOR WILL NOT RUN:
1.
Check to be sure that the disconnect switch is in the ON position and that the selector switch is in
the START position.
2.
Check to be sure that the plant voltage and phase correspond to the machine voltage and phase.
3.
Check the line wiring connections at the starter. For the wiring diagram, SEE FIG. 4 ON
PAGE 15.
4.
Check the line voltage at the starter. If the correct line voltage is present at the starter, either the
starter or the motor is defective. Contact your local dealer or the factory.
B.
MOTOR RUNS, BUT THE MACHINE WILL NOT CYCLE WHEN DEPRESSING THE FOOT
PEDAL:
1.
Check the motor rotation. It should be counterclockwise when viewed from the shaft end of the
motor.
2.
Check the selector switch. It must be in either the PUNCH or the SHEAR position or the machine
will not move.
3.
Check the stroke control adjustment and make sure that only one limit switch is in contact with
the contact blocks. If both limit switches are in contact with the contact blocks, the machine will
not move. Loosen the stroke control handles and move the contact blocks. Try the machine again.
4.
Check the fuses in the control box. There are two fuses in line on the primary side. Remove the
fuses and check them with an Ohm meter and replace them, if necessary. For the primary side,
use a Bussman FNQ-R1 600 volt or equivalent. For the secondary side, use a Bussman FLM-1 6/10
or equivalent.
5.
Check the limit switches. For procedures, REFER TO SECTION 8.2.
6.
No power from the transformer: Check the voltage across the transformer secondary terminals.
It should read 110 to 120 volts.
7.
The solenoid on the control valve is not functioning: REFER TO SECTION 8.3.
8.
The foot pedal switch is not functioning properly: A voltage test may be run on the terminal strip
in the control box to determine if the foot switch is working properly.
WARNING: THERE IS LINE VOLTAGE PRESENT IN THE CONTROL BOX WHEN THE
MACHINE IS POWERED. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED
ELECTRICIAN.
Содержание 9012-24M
Страница 10: ...Page 9 FIGURE 1 ...
Страница 12: ...Page 11 FIGURE 2 ...
Страница 16: ...Page 15 FIGURE 4A ...
Страница 17: ...Page 16 FIGURE 4B ...
Страница 18: ...Page 17 FIGURE 4C ...
Страница 22: ...Page 21 FIGURE 6 ...
Страница 24: ...Page 23 FIGURE 7 ...
Страница 35: ...Page 34 THIS PAGE LEFT BLANK INTENTIONALLY ...
Страница 40: ...Page 39 FIGURE 15 ...
Страница 42: ...Page 41 FIGURE 16 ...
Страница 48: ...Page 47 FIGURE 20 ...
Страница 54: ...Page 53 FIGURE 24 ...
Страница 56: ...Page 55 FIGURE 25 ...
Страница 62: ...Page 61 FIGURE 27 ...
Страница 66: ...Page 65 FIGURE 29 ...
Страница 68: ...Page 67 FIGURE 30 ...
Страница 74: ...Page 73 FIGURE 32 ...
Страница 78: ...Page 77 FIGURE 34 ...
Страница 80: ...Page 79 FIGURE 35 ...
Страница 82: ...Page 81 FIGURE 36 ...
Страница 84: ...Page 83 FIGURE 37 ...
Страница 86: ...Page 85 FIGURE 38 ...
Страница 90: ...Page 89 FIGURE 41 ...
Страница 92: ...Page 91 FIGURE 42 ...
Страница 93: ...Page 92 FIGURE 43 ...
Страница 96: ...Page 95 THIS PAGE LEFT BLANK INTENTIONALLY ...
Страница 98: ...Page 97 FIGURE 46 ...
Страница 100: ...Page 99 FIGURE 47 ...