6-10
Close and Reclose Logic
Date Code 20020215
SEL-351R Instruction Manual
SEL-351R(2) Recloser Control
The SEL-351R(2) checks that Bus 2 voltage is hot, the transmission line voltage is hot, and in
synchronism after the reclosing relay open interval times out, before allowing circuit breaker
52/2 to be reclosed. This requires reclose supervision settings:
79CLSD = 0.00 cycles
(only one check)
79CLS
=
25A1
where:
25A1
= selected Bus 2 phase voltage (VA, VB, or VC) is in synchronism with
monitored single-phase transmission line voltage (channel VS) and both are
hot
Other Setting Considerations for SEL-351R(1) and SEL-351R(2) Recloser Controls
Refer to
Skip Shot and Stall Open Interval Timing Settings (79SKP and 79STL, respectively)
in the following
Reclosing Relay
subsection.
SEL
OGIC
control equation setting 79STL stalls open interval timing if it asserts to logical 1. If
setting 79STL is deasserted to logical 0, open interval timing can continue.
The SEL-351R(1) has no intentional open interval timing stall condition (circuit breaker 52/1
closes first after a transmission line fault):
79STL =
0
(numeral
0)
The SEL-351R(2) starts open interval timing after circuit breaker 52/1 at the remote end has
reenergized the line. The SEL-351R(2) has to see Bus 2 hot, transmission line hot, and in
synchronism across open circuit breaker 52/2 for open interval timing to begin. Thus,
SEL-351R(2) open interval timing is stalled when the transmission line voltage and Bus 2
voltage are not in synchronism across open circuit breaker 52/2:
79STL =
!25A1
[=NOT(25A1)]
Note:
A transient synchronism check condition across open circuit breaker 52/2 could possibly
occur if circuit breaker 52/1 recloses into a fault on one phase of the transmission line.
The other two unfaulted phases would be briefly energized until circuit breaker 52/1 is
tripped again. If channel VS of the SEL-351R(2) Relay is connected to one of these
briefly energized phases, synchronism check element 25A1 could momentarily assert to
logical 1.
So that this possible momentary assertion of synchronism check element 25A1 does not
cause any inadvertent reclose of circuit breaker 52/2, make sure the open interval timers
in the SEL-351R(2) are set with some appreciable time greater than the momentary
energization time of the faulted transmission line. Or, run the synchronism check
element 25A1 through a programmable timer before using it in the preceding 79CLS and
79STL settings for the SEL-351R(2) (see Figure 7.23 and Figure 7.24). Note the built-in
3-cycle qualification of the synchronism check voltages shown in Figure 3.24.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......