3-16
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Date Code 20020215
SEL-351R Instruction Manual
Figure 3.13: Levels 5 Through 6 Negative-Sequence Instantaneous Overcurrent Elements
T
IME
-O
VERCURRENT
E
LEMENTS
Phase Time-Overcurrent Elements
Two phase time-overcurrent elements, 51P1T and 51P2T, are available. The elements are
enabled with the E51P enable setting as follows:
Table 3.1: Available Phase Time-Overcurrent Elements
Time-Overcurrent
Element
Enabled with
Setting
Operating Current
See Figure
51P1T
51P2T
E51P = 1 or 2
E51P = 2
I
P
, maximum of A-, B-, and
C-phase currents
The following is an example of 51P1T element operation. 51P2T is similar.
Settings Ranges