Date Code 20020215
Close and Reclose Logic
6-15
SEL-351R Instruction Manual
Open Interval Timers
The reclose enable setting, E79, determines the number of open interval time settings that can
be set. For example, if setting E79 = 3, the first three open interval time settings in Table 6.2,
are made available for setting.
If an open interval time is set to zero, then that open interval time is not operable, and neither
are the open interval times that follow it.
In the factory settings in Table 6.2, the open interval 4 time setting 79OI4 is the first open
interval time setting set equal to zero:
79OI4 =
0.00
cycles
Thus, open interval time 79OI4 is not operable. In the factory settings, open interval time
79OI4 is set to zero. But if the settings were:
79OI3 =
0.00
cycles
79OI4
= 900.00 cycles (set to some value other than zero)
both open interval time 790I3 and 79OI4 would both be inoperative, because a preceding open
interval time is set to zero (i.e., 79OI3 = 0.00).
If open interval 1 time setting, 79OI1, is set to zero (79OI1 = 0.00 cycles), no open interval
timing takes place, and the reclosing relay is defeated.
The open interval timers time consecutively; they do not have the same beginning time
reference point. In the above factory settings, open interval 1 time setting, 79OI1, times first. If
the subsequent first reclosure is not successful, then open interval 2 time setting, 79OI2, starts
timing. If the subsequent second reclosure is not successful, the relay goes to the Lockout State.
See the example time line in Figure 6.6.
Figure 6.6: Reclosing Sequence from Reset to Lockout with Example Settings
SEL
OGIC
control equation setting 79STL (stall open interval timing) can be set to control open
interval timing [see
Skip Shot and Stall Open Interval Timing Settings (79SKP and 79STL,
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......