Date Code 20020215
Standard Event Reports and SER
12-29
SEL-351R Instruction Manual
Figure 12.4: Derivation of Phasor RMS Current Values From Event Report Current
Values
In Figure 12.4, note that two rows of current data from the event report in Figure 12.2, 1/4 cycle
apart, can be used to calculate phasor RMS current values. In Figure 12.4, at the present sample,
the phasor RMS current value is:
IA = 991 A
∠
-33.7
°