Date Code 20020215
Breaker/Recloser Monitor, Battery System Monitor,
8-1
Metering, and Load Profile Functions
SEL-351R Instruction Manual
SECTION 8: BREAKER/RECLOSER MONITOR, BATTERY
SYSTEM MONITOR, METERING, AND LOAD
PROFILE FUNCTIONS
I
NTRODUCTION
The SEL-351R Recloser Control monitoring functions include:
•
Breaker/Recloser Contact Wear Monitor
•
Battery System Monitor
In addition to instantaneous metering, the SEL-351R metering functions include:
•
Demand Metering
•
Energy Metering
•
Maximum/Minimum Metering
This section explains these functions in detail.
B
REAKER
/R
ECLOSER
C
ONTACT
W
EAR
M
ONITOR
The breaker/recloser contact wear monitor in the SEL-351R provides information that helps in
scheduling circuit breaker or recloser maintenance. This monitoring function accumulates the
number of internal and external trip operations and integrates the number of close-open
operations and the per-phase current during each opening operation. The SEL-351R compares
the integrated close-open information to a pre-defined breaker or recloser maintenance curve to
calculate the percent contact wear on a per-pole basis. The SEL-351R updates and stores the
contact wear information, and the number of trip operations, in non-volatile memory. You can
view this information through the front-panel display and by communicating with the SEL-351R
through any serial communication port with a computer.
Individual phase Breaker Contact Wear bits, BCWA, BCWB, and BCWC, assert when the
contact wear percentage on their respective phases reaches 100%. You can use these individual
phase elements or the combined result of these elements, BCW (asserts when BCWA or BCWB
or BCWC assert), in a SEL
OGIC
®
control equation to alarm or control other functions, such as
block reclosing.
Enable the breaker/recloser contact wear monitor with the global EZ setting
Recloser Wear
Monitor (AUTO, Y, N)
. Access this setting with the SET FZ (global EZ settings) command from
Access Level E (EZ) or Access Level 2. The contact wear monitor is configured as follows:
•
Recloser Wear Monitor (AUTO, Y, N)
= N
disables the contact wear monitor. Setting
EBMON in Table 8.1 is automatically set EBMON = N and the rest of the settings in
Table 8.1 are hidden.
•
Recloser Wear Monitor (AUTO, Y, N)
= Y
enables the contact wear monitor. Setting
EBMON in Table 8.1 is automatically set EBMON = Y, but you must then use the
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......