6-22
Close and Reclose Logic
Date Code 20020215
SEL-351R Instruction Manual
Overall, settings 79DTL or 79DLS are needed to take the relay to the Lockout State (or to last
shot) for immediate circumstances.
Skip Shot and Stall Open Interval Timing Settings (79SKP and 79STL, respectively)
The skip shot setting 79SKP causes a reclose shot to be skipped. Thus, an open interval time is
skipped, and the next open interval time is used instead.
If 79SKP = logical 1 at the instant of successful reclose initiation (see preceding discussion on
settings 79RI and 79RIS), the relay increments the shot counter to the next shot and then loads
the open interval time corresponding to the new shot (see Table 6.3). If the new shot is the “last
shot,” no open interval timing takes place, and the relay goes to the Lockout State if the circuit
breaker is open (see
After successful reclose initiation, open interval timing does not start until allowed by the stall
open interval timing setting 79STL. If 79STL = logical 1, open interval timing is stalled. If
79STL = logical 0, open interval timing can proceed.
If an open interval time has not yet started timing (79STL = logical 1 still), the 79SKP setting is
still processed. In such conditions (open interval timing has not yet started timing), if
79SKP = logical 1, the relay increments the shot counter to the next shot and then loads the
open interval time corresponding to the new shot (see Table 6.3). If the new shot turns out to be
the “last shot,” no open interval timing takes place, and the relay goes to the Lockout State if
the circuit breaker is open (see
If the relay is in the middle of timing on an open interval and 79STL changes state to 79STL =
logical 1, open interval timing stops where it is. If 79STL changes state back to 79STL =
logical 0, open interval timing resumes where it left off. Use the OPTMN Relay Word bit to
monitor open interval timing (see
Monitoring Open Interval and Reset Timing
subsection).
Factory Settings Example
The skip shot function is not enabled in the factory settings:
79SKP =
0
(numeral
0)
The stall open interval timing factory setting is:
79STL =
TRIP
After successful reclose initiation, open interval timing does not start as long as the trip
condition is present (Relay Word bit TRIP = logical 1). As discussed previously, if an open
interval time has not yet started timing (79STL = logical 1 still), the 79SKP setting is still
processed. Once the trip condition goes away (Relay Word bit TRIP = logical 0), open interval
timing can proceed.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......