Date Code 20020215
Factory-Set Logic
1-1
SEL-351R Instruction Manual
SECTION 1:
FACTORY-SET LOGIC
I
NTRODUCTION
This section describes the factory-set logic (SEL
OGIC
®
control equations, set with the SET L n
command) that makes the SEL-351R Recloser Control operate as a recloser control.
Section 3:
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
through
Section 9:
Setting the SEL-351R Recloser Control
provide more settings information and settings variation
details. Important: Use this manual in conjunction with the
SEL-351R Quick-Start Installation
and User’s Guide
.
Factory Default Settings
Factory default settings are listed under subsection
SHO Command (Show/View Settings)
in
Section 10: Serial Port Communications and Commands
.
Installation Variations and Logic Changes
For traditional recloser control installations (see Figure 1.31), none of the factory-set logic has to
be changed. However, for other recloser control installation variations (see Figure 1.32 through
Figure 1.34), some changes might be made to the factory-set logic, as detailed in the text
accompanying these figures. Also, if the SEL-351R were applied in “nonstandard” applications
(e.g., at a cogeneration interconnection point), changes would probably be made to the factory-
set logic.
Section 9: Setting the SEL-351R Recloser Control
provides details on making
settings changes.
EZ Settings vs. “Regular” Settings
The
Settings
section in the
SEL-351R Quick-Start Installation and User’s Guide
describes:
•
EZ recloser control settings (set with SET EZ n command)
•
EZ global settings (set with SET FZ command)
Section 9: Setting the SEL-351R Recloser Control
describes:
•
“regular” settings (set with SET n command)
•
“regular” global settings (set with SET G command)
The EZ recloser control settings are a subset of the “regular” settings, but if the EZ recloser
control settings are enabled for a specific settings group n (n = 1–6), then the corresponding EZ
recloser control settings override and change certain “regular” settings for that settings group.
The EZ global settings override certain “regular” global settings if EZ recloser control settings
are enabled for at least settings group 1. Global setting EZGRPS determines if EZ recloser
control settings are enabled for a particular setting group.
The correlation between EZ recloser control settings and “regular” settings is given in Table 1.1.
The correlation between EZ global settings and “regular” global settings is also given at the end
of Table 1.1.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......