viii
Manual Change Information
Date Code 20020215
SEL-351R Instruction Manual
Revision
Date
Summary of Revisions
Section 3:
-
Added clarifying reference to introduction and in
Frequency Elements
subsection.
Section 4:
-
Removed a Setting Description in
Settings Ranges
(under setting ZLR).
-
Revised the example at the end of
Apply Load-Encroachment to a Phase
Time-Overcurrent
.
Section 7:
-
Added clarifying reference in the
Recloser Trip and Close Circuits
.
-
Expanded Figure 7.29 to show the 22000ìF capacitor in parallel with the
24 Vdc supply to the recloser trip and close circuitry.
Section 8:
-
Changed battery amp-hour rating from 6.5 to 8.0 Ah (factory-shipped batteries
have changed as detailed in the
Battery Replacement
subsection in the
Battery
section of the
SEL-351R Quick-Start Installation and User’s Guide
).
Note:
The Battery Amp-hours setting was not changed in the factory-default
global settings listed in
SHO Command
(Show/View Settings) in
Section 10:
Serial Port Communications and Commands
– it remains at 6.5 Ah. This is a
conservative setting for the new 8.0 Ah batteries. The user can change the
Battery Amp-hours setting to 8.0 Ah, if desired.
981203
This revision includes the following changes:
-
Corrected
Figure 1.22
in
Section 1: Factory-Set Logic
.
-
SEL
OGIC
Control Equations torque control settings can no longer be set
directly to logical 0, as explained in the overcurrent element sections of
Section 3: Overcurrent, Voltage, Synchronism Check, Frequency, and
Power Elements
and the SEL
OGIC
Control Equations settings sheets in the
back of
Section 9: Setting the SEL-351R Recloser Control
.
-
SEL
OGIC
Control Equations drive-to-lockout setting 79DTL has a 60-cycle
dropout time, as explained in
Section 6: Close and Reclose Logic
.
-
Corrected typographical error in
Factory Settings Example
in
Section 6:
Close and Reclose Logic
(no date code change)
.
-
Corrected typographical error in
Determining the Size of the Load Profile
Buffer
in
Section 8: Breaker/Recloser Monitor, Battery System Monitor,
metering, and Load Profile Functions
(no date code change)
.
-
More SEL
OGIC
Control Equations settings limitations information added to
Appendix G: Setting SEL
OGIC
Control Equations
.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......