2-2
Additional Installation Details
Date Code 20020215
SEL-351R Instruction Manual
O
UTPUT
C
ONTACT
J
UMPERS
Table 2.1 shows the correspondence between output contact jumpers and the output contacts they
control. Figure 19 in the
Communications
section of the
SEL-351R Quick-Start Installation
and User’s Guide
shows the exact location and correspondence. With a jumper in the A
position, the corresponding output contact is an “a” type output contact. An “a” type output
contact is open when the output contact coil is deenergized and closed when the output contact
coil is energized. With a jumper in the B position, the corresponding output contact is a “b” type
output contact. A “b” type output contact is closed when the output contact coil is deenergized
and open when the output contact coil is energized. These jumpers are soldered in place.
In Figure 2.1, note that the ALARM output contact is a “b” type output contacts and the other
output contacts are all “a” type output contacts. This is how these jumpers are configured in a
standard SEL-351R Recloser Control shipment. Refer to corresponding Figure 7.27 for
examples of output contact operation for different output contact types.
Table 2.1: Output Contact Jumpers and Corresponding Output Contacts
Output Contact
Jumpers
Corresponding
Output Contacts
JMP21–JMP29 (but not JMP23)
ALARM–OUT101
“E
XTRA
A
LARM
” O
UTPUT
C
ONTACT
C
ONTROL
J
UMPER
The SEL-351R has a dedicated alarm output contact (labeled ALARM—see Figure 2.1). Often
more than one alarm output contact is needed for such applications as local or remote
annunciation, backup schemes, etc. An extra alarm output contact can be had without the
addition of any external hardware.
The output contact next to the dedicated ALARM output contact can be converted to operate as
an “extra alarm” output contact by moving a jumper on the main board (see Table 2.2).
Table 2.2: “Extra Alarm” Output Contact and Corresponding Controlling Jumper
“Extra Alarm”
Output Contact
Controlling
Jumper
OUT107 JMP23
The position of the jumper controls the operation of the output contact next to the dedicated
ALARM output contact. With the jumper in one position, the output contact operates regularly.
With the jumper in the other position, the output contact is driven by the same signal that
operates the dedicated ALARM output contact (see Table 2.3).
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......