
H-14
Distributed Network Protocol (DNP) V3.00
Date Code 20020215
SEL-351R Instruction Manual
Binary inputs (objects 1 and 2) are supported as defined by the previous table. Binary inputs 0–
499 and 1000–1023 and 1025 are scanned approximately once per second to generate events.
When time is reported with these event objects, it is the time at which the scanner observed the
bit change. This may be significantly delayed from when the original source change and should
not be used for sequence-of-events determination.
In order to determine an element’s point index, consult the Relay Word Bits table in
Section 9:
Setting the SEL-351R Recloser Control.
Locate the element in question in the table and note
the Relay Word row number. From that row number, subtract the row number of the first Relay
Word row (usually 2) and multiply that result by 8. This is the index of the right-most element
of the Relay Word row of the element in question. Count over to the original element and add
that to get the point index. Binary Inputs 500–999 are derived from the Sequential Events
Recorder (SER) and carry the time stamp of actual occurrence. Static reads from these inputs
will show the same data as a read from the corresponding index in the 0–499 group. Only points
that are actually in the SER list (SET R) will generate events in the 500–999 group.
Analog Inputs (objects 30 and 32) are supported as defined by the preceding table. The values
are reported in primary units. Analog inputs 28–35, 42–57, 64–79, 86–104, and 106 are further
scaled according to the DECPLM setting (e.g., if DECPLM is 3, then the value is multiplied by
1000). Analog inputs 58–63, 80–85, 107, 115–119, and the even-numbered points in 0–7 and
16–21 (current magnitudes) are scaled according to the DECPLA setting. The even-numbered
points in 8–15 and 22–27 (voltage magnitudes) are scaled according to the DECPLV setting.
Analog inputs 36–41, 108, and the odd-numbered points in 0–27 (angles) are scaled by 100, and
input 114 is scaled by 10. The remaining analogs are not scaled.
Event-class messages are generated whenever an input changes beyond the value given by the
ANADB setting. The dead-band check is done after any scaling is applied. The angles (the odd
numbered points in 0–27) will only generate an event if, in addition to their dead-band check, the
corresponding magnitude (the preceding point) contains a value greater than the value given by
the ANADB setting.
In standard mode, analog inputs are scanned at approximately a 1-second rate, except for analogs
105
–
113. During a scan, all events generated will use the time the scan was initiated. Analogs
105
–
113 are derived from the history queue data for the most recently read fault. In standard
mode, analogs 105
–
113 do not generate event messages. In extended mode, events for these
inputs will use the time the scan was initiated. Analog input 115 is derived from the history
queue. Analog 105 is a 16-bit composite value, where the upper byte is defined as follows:
Value Event
Cause
1
Trigger command
2
Pulse command
4
Trip element
8
ER element
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......